Parameters 157
Fieldbus A The start and stop commands are taken from fieldbus adapter
A.
4
Embedded fieldbus The start and stop commands are taken from the embedded
fieldbus interface.
5
79.11 Manual input
source 1
Selects source 1 for the parameter 79.10 Operating mode.
DI1
Not selected 0 (always off). 0
Selected 1 (always on). 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Other [bit] Source selection (see Terms and abbreviations on page 64). -
79.12 Manual input
source 2
Selects source 2 for the parameter 79.10 Operating mode.
See parameter 79.11 Manual input source 1.
DI2
79.15 Enable tank level
operation
Selects the source for the tank level operation enable signal.
0 = Disabled.
1 = Enabled.
Notes:
• Works only with
Manual In 1 Start; stop
operating mode.
See parameter 79.10 Operating mode.
• Enables only when the drive is not in running mode.
Disable
Disable 0 = Tank level sensor operation is disabled. 0
Enable 1 = Tank level sensor operation is enabled. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Other [bit] Source selection (see Terms and abbreviations on page 64). -
79.17 Tank low sensor Selects the source for tank low level sensor enable signal.
0 = Not selected
1 = Selected.
DI5
Not selected 0 (always off). Tank low level sensor is not activated. 0
Selected 1 (always on). Tank low level sensor is activated. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
No. Name/Value Description Def/FbEq16
ACQ80 FW.book Page 157 Thursday, February 14, 2019 11:33 AM

Table of Contents

Other manuals for ABB ACQ80-04

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ80-04 and is the answer not in the manual?

ABB ACQ80-04 Specifications

General IconGeneral
BrandABB
ModelACQ80-04
CategoryDC Drives
LanguageEnglish

Related product manuals