304 Actual signals and parameters
AI1HI2 ORDLY State change when AI1 value > par. 8413 SEQ VAL 2 HIGH
value or after delay time defined by parameter 8424 ST1
CHANGE DLY has elapsed.
34
AI2LO2 ORDLY State change when AI2 value < par. 8414 SEQ VAL 2 LOW
value or after delay time defined by parameter 8424 ST1
CHANGE DLY has elapsed.
35
SUPRV1
OVER
Logic value according to supervision parameters
32013203. See parameter group 32 SUPERVISION.
36
SUPRV2
OVER
Logic value according to supervision parameters
32043206. See parameter group 32 SUPERVISION.
37
SUPRV3
OVER
Logic value according to supervision parameters
32073209. See parameter group 32 SUPERVISION.
38
SUPRV1
UNDER
See selection SUPRV1 OVER.39
SUPRV2
UNDER
See selection SUPRV2 OVER.40
SUPRV3
UNDER
See selection SUPRV3 OVER.41
SPV1OVRORD
LY
State change according to supervision parameters
32013203 or when delay time defined by parameter 8424
ST1 CHANGE DLY has elapsed. See parameter group 32
SUPERVISION.
42
SPV2OVRORD
LY
State change according to supervision parameters
32043206 or when delay time defined by parameter 8424
ST1 CHANGE DLY has elapsed. See parameter group 32
SUPERVISION.
43
SPV3OVRORD
LY
State change according to supervision parameters
32073209 or when delay time defined by parameter 8424
ST1 CHANGE DLY has elapsed. See parameter group 32
SUPERVISION.
44
SPV1UNDORD
LY
See selection SPV1OVRORDLY.45
SPV2UNDORD
LY
See selection SPV2OVRORDLY.46
SPV3UNDORD
LY
See selection SPV3OVRORDLY.47
CNTR OVER State change when counter value exceeds the limit defined
by par. 1905 COUNTER LIMIT. See parameters
19041911.
48
CNTR UNDER State change when counter value is below the limit defined
by par. 1905 COUNTER LIMIT. See parameters
19041911.
49
LOGIC VAL State change according to logic operation defined by
parameters 84068410
50
All parameters
No. Name/Value Description Def/FbEq

Table of Contents

Other manuals for ABB ACS355 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS355 series and is the answer not in the manual?

ABB ACS355 series Specifications

General IconGeneral
Power Range0.37 to 22 kW
Protection ClassIP20
Output Frequency0 to 500 Hz
Braking ChopperBuilt-in
Control MethodScalar control, Vector control
Ambient Temperature-10 to +50 °C
Communication ProtocolsModbus, CANopen
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature
Cooling MethodAir-cooled
Number of Phases3-phase