ControlMaster CM30
Universal process controller,
1
/
4
DIN
16 DS/CM30–EN Rev. L | ControlMaster CM30 | Universal process controller,
1
/
4
DIN
Setpoints
Local:
4, selectable via digital input or front panel
Remote:
selectable via digital input or front panel keys
Auto tune
On-demand calculation of control settings
Process alarms
Number:
—8
Type s :
High / Low process
High / Low latch
Source
Fully configurable
(for example – PV, Analog input, Math block inbuilt, OP
control loop deviation)
Hysteresis:
Level and time
Alarm enable:
Enable / Disable individual alarms via a digital signal
Acknowledgement
Via front panel keys or digital signals
Real-time alarms
Number:
—2
Programmable:
—Time
—Day
—Duration
Math blocks
Number:
—8
Operators:
+, –, x, /
Average, Maximum, Minimum
High / Low / Median select
Square root
Multiplexer
Delay timers
Number:
—2
Programmable:
—Delay
—Duration
Logic equations
Number:
—8
Elements:
15 per equation
Operators:
OR, AND, NOR, NAND, NOT, EXOR
Custom linearizer
Number:
—2
Elements:
20 breakpoints