DescriptionExample
value
NameIndex
Sets the type of the event that the FSO
module generates and sends to the
drive after external requests that end
to a successful activation of the drive
STO function (STO, SSE or SS1).
Warning
1)
STO indication
ext request
FSO-
GEN.61
None, Warning, Event: You do not have
to reset the drive/inverter unit.
Fault: You have to reset the drive/invert-
er unit.
1)
The value does not affect the SMT function, but other safety functions in
the FSO module can require a certain value.
■ Parameters for the STO function
These parameters are related to the STO function of the FSO module.
With stop category 0, the FSO module activates the STO function in
overtemperature situations. Also, the FSO module can activate the
STO function in fault situations.
DescriptionExample
value
NameIndex
Sets the acknowledgement method
used in the STO, SSE and SS1 func-
tions.
AutomaticSTO acknow-
ledgement
STO.02
Automatic: The FSO module resets the
STO function automatically after the
STO request is removed.
Manual: The FSO module reads the
external acknowledgement signal
through the digital input defined by
parameter FSOGEN.42.
Sets the digital input that is connected
to the primary input of the STO func-
tion.
NoneSTO input ASTO.11
In this example, this parameter has
value None.
56 Parameter settings