Low Voltage Products & Systems 149
ABB Inc. • 888-385-1221 • www.abb-control.com AC 1006.9 - 5/03
Chapter 10 - Functions
10:57 Initial voltage, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Init Volt1
This parameter makes it possible to set the initial voltage for the first
parameter set.
10:58 Current limit, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Curr Lim1
This parameter makes it possible to set the current limit level for the
first parameter set.
10:59 Setting current, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./1st Set Ie
This parameter makes it possible to set the rated motor current for
the first parameter set.
Parameter
text
Default
value
Setting
range
Description
Init Volt1 30% 30… 70%
First
sequence,
initial voltage
for start
ramp
Parameter
text
Default
value
Setting
range
Description
Curr Lim1
4xI
e
2.0… 5.0xI
e
First
sequence,
current limit
Parameter
text
Default
value
Setting
range
Description
1st Set Ie Ir
9… 1380A
divided into
19
overlapping
ranges
First
sequence,
current limit