Disturbance records
Fault records
Events
Load profile record
6.1.3.1 Creating disturbance recordings
Normally disturbance recordings are triggered by the protection relay applications but
the recording can also be triggered manually.
1. Select Main menu/Disturbance records.
2.
Select Trig recording with
or .
3.
Press , change the value with or and press again.
A070861 V3 EN
Figure 67: Changing the value
The disturbance recorder is now triggered.
6.1.3.2 Monitoring disturbance recorder data
Upload individual disturbance recordings from the protection relay with the PCM600
software to monitor disturbance recorder data.
1. Select Main menu/Disturbance records.
All the disturbance recorder information is listed.
2.
Scroll the view with or .
The following items are listed in the view:
Section 6 1MRS758754 B
Operating procedures
90 REC615 and RER615
Operation Manual