1MAC309294-MB F Section 7
Measurement functions
RER620 407
Technical Manual
7.1.10.4 Settings
Table 370: P,SP,E Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=Enable
5=Disable
1=Enable Operation Off / On
Power unit Mult 3=Kilo
6=Mega
3=Kilo Unit multiplier for presentation of the power related values
Energy unit Mult 3=Kilo
6=Mega
3=Kilo Unit multiplier for presentation of the energy related values
Active power Dir 1=Forward
2=Reverse
1=Forward Direction of active power flow: Forward, Reverse
Reactive power Dir 1=Forward
2=Reverse
1=Forward Direction of reactive power flow: Forward, Reverse
Forward Wh Initial 0...999999999 1 0 Preset Initial value for forward active energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value for reverse active energy
Forward WArh Initial 0...999999999 1 0 Preset Initial value for forward reactive energy
Reverse WArh Initial 0...999999999 1 0 Preset Initial value for reverse reactive energy