12 1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect
Publication 1732E-IN010C-EN-E - June 2013
Enable QuickConnect
To enable QuickConnect for the Ethernet ports, use the RSLogix 5000 software Module
QuickConnect tab and check the Enable QuickConnect option. For more information on
the QuickConnect system set up, refer to Ethernet QuickConnect Application Technique,
publication ENET-AT001
.
After the QuickConnect feature is set to "on", the module must be power cycled.
QuickConnect is active during the next connection.
Once active, the QuickConnect feature automatically sets all Ethernet ports to:
Speed = 100 Mbps
•Duplex = Full
•Auto-negotiate = Off
Automatic Cross-over Cable Detection (Auto-MDIX) = Off
If you configure BootP or DHCP, QuickConnect changes the configuration to retain the
current IP address. Disabling the QuickConnect feature automatically sets all Ethernet
ports to Automatic Cross-over Cable Detection (Auto-MDIX) = On.
To reset the Ethernet ports to Auto-negotiate or the IP address to DHCP request, you can:
change the setting on the module web page
change the setting in the RSLogix 5000 software
perform a factory reset

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1732E ArmorBlock Series and is the answer not in the manual?

Allen-Bradley 1732E ArmorBlock Series Specifications

General IconGeneral
BrandAllen-Bradley
Model1732E ArmorBlock Series
CategoryControl Unit
LanguageEnglish

Related product manuals