EN: Installation Sheet
Description
The DM2010 manual call point is designed for use in Aritech
analogue addressable fire alarm systems and include models
for indoor and outdoor use.
Installation
Caution: This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any other
applicable local authority laws.
Electrical connections
Connect to the DM2010 connection block (Figure
2) as follows:
1. Line in (positive)
2. Line out (positive)
3. Line in (negative)
4. Line out (negative)
Addressing
Use the DIP switch (Figure 1) to allocate a device address
from 1 to 128 (see page 3).
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Voltage
17 to 28 VDC
Current
consumption
Standby
Alarm
max. 250 ųA
max. 2.5 mA
Cable size
Minimum
Maximum
0.8 mm2
2.5 mm2
IP rating
DM2010, DM2010-18
DM2010E, DM2010E-18
IP24D
IP67
Operating temperature
DM2010, DM2010-18
DM2010E, DM2010E-18
10°C to +55°C
25°C to +70°C
Storage temperature
DM2010, DM2010-18
DM2010E, DM2010E-18
10°C to +70°C
25°C to +70°C
Relative humidity
10% to 95% noncondensing
Dimensions (W × H × D)
DM2010, DM2010-18
DM2010E, DM2010E-18
89 x 93 x 27.5 mm [1]
97.5 x 93 x 27.5 mm [1]
Weight
DM2010, DM2010-18
DM2010E, DM2010E-18
180 g
350 g
[1] Excluding surface mount