AB-6256
1
Specifications/Instructions
Insertion Type CO
2
Concentration Transmitter
Model CY8100C1000 (Main Unit)
Part No. 83165722-002 (Assembly Kit)
General
Model CY8100C in combination with Part No. 83165722-002
is an insert type CO
2
concentration transmitter used for
detecting concentration of carbon dioxide (CO
2
) in ducts.
This product can be used in a wide range of applications
such as monitoring of CO
2
concentration in return ducts and
the control of outdoor air intake.
Features
• Non-dispersive infrared absorption method (NDIR)
• Linear output signal in 1-5 V DC range
• Long-term stability
Model Number and Part Number
For the insertion type CO
2
concentration transmitter, both of
the following items are required.
Model/Part number Description
CY8100C1000 Main unit
83165722-002 Assembly kit
- Sampling probe
- Gasket, 2 screws, 2 washers
- Cable assembly
Optional Parts
Part number Description
83165722-002 Assembly kit (for replacement)
- Sampling probe
- Gasket, 2 screws, 2 washers
- Cable assembly
83104511-001 Zero calibration service bag
(CO
2
zero calibration gas generator)
83104981-001 Zero calibration service cylinder
(CO
2
zero calibration gas cylinder)
Specifications (1/2)
Item Specification
Measuring range 0 to 2000 ppm CO
2
Concentration
Operating principle Non-dispersive infrared absorption
method (NDIR)
Measuring accuracy ± (50 ppm + 5 % of reading)
Drift Continuously ON: ±150 ppm/year
Continuously OFF (reference value):
±15 ppm/48 hours at 50 %RH
Time constant 15 min. or less (windless)
3 min. or less (0.6 m/s wind)
Operation CO
2
concentration: 0 to 2000 ppm
Temperature: 0 to 50 °C
Humidity: 0 to 95 %RH (non-condensing)
Environmental
conditions
Transport/
Storage
Temperature: -20 to 50 °C
Humidity: 0 to 95 %RH (in moisture-
proof package)
Power supply voltage 24 V AC ± 10 %, 50 to 60 Hz
Power consumption Max. 3 VA
Output signal 1 to 5 V DC (linear with 0-2000 ppm
CO
2
concentration)
Allowable load resistance 5 kΩ or more
Wiring Power supply: 2-wire
CO
2
concentration output: 2-wire
(2/2)
Item Specification
Initial stabilizing time
Continuously OFF for 48 hours or longer:
Approx. 10 days (∗ Product in a
package is exceptional.)
Other than the above: Approx. 3 days
Allowable vibration 4.9 m/s
2
(10 to 150 Hz)
Insulation resistance 100 MΩ or higher at 500 V DC
(between the case and each lead wire)
Enclosure rating (main unit)
IEC IP65 (dust-proof and water-proof)
Weight Approx. 350 g
Material Main unit
- Case: PC + ABS plastic
(Bayblend
®
FR90)
- Cover: PC Makrolon
®
6555
Sampling probe: PC Makrolon
®
6555
Application Indoor duct, chamber