Parameterization and commissioning
BK3xx040 Version: 4.3.0
Complex function
module
Description Associated CfgData (as
hex code)
KL5001 compact KL5001 - only the 32 bit input value is transmitted 0x93 (in GSD file)
0xD1 (alternatively)
KL5001 complex KL5001 - 40 bits of input/output are transmitted, so that
access can be had to the terminal's registers in addition to
transmission of the 40 bit input value
0xB4 (in GSD file)
0xB5 (alternatively)
0xF2 (alternatively)
KL5051 KL5051 0xB5 (in GSD file)
0xF2 (alternatively)
KL5101 KL5101 0xB5 (in GSD file)
0xF2 (alternatively)
KL5111 KL5111 0xB5 (in GSD file)
0xF2 (alternatively)
KL5121 KL5121 0xB5 (in GSD file)
0xF2 (alternatively)
KL5151 KL5151 0xB5 (in GSD file)
0xF2 (alternatively)
KL5302 KL5302 0xB5 (in GSD file)
0xF2 (alternatively)
KL6001 KL6001 0xB5 (in GSD file)
0xF2 (alternatively)
KL6011 KL6011 0xB5 (in GSD file)
0xF2 (alternatively)
KL6021 KL6021 0xB5 (in GSD file)
0xF2 (alternatively)
KL6051 compact KL6051 - only the 32 input bits and 32 output bits are
transmitted
0xB3 (in GSD file)
0xF1 (alternatively)
KL6051 complex KL6051 - 48 input bits and 48 output bits are transmitted, so
that in addition to the 40 input bits and the 40 output bits,
access can also be had to the terminal's registers
0xB5 (in GSD file)
0xF2 (alternatively)
KL6061 KL6061 0xBA (in GSD file)
0xF5 (alternatively)
KL6201 (PAB 6) KL6201 - 6 bytes input and output process data is
transferred (ASI slaves 1-11)
0x35 (in GSD file)
KL6201 (PRM PAB
6)
KL6201 - 6 bytes parameter interface and 6 bytes input and
output process data is transferred (ASI slaves 1-11)
0xF2,0x35 (in GSD file)
KL6201 (PAB 16) KL6201 - 16 bytes input and output process data is
transferred (ASI slaves 1-31)
0x3F (in GSD file)
KL6201 (PRM PAB
16)
KL6201 - 6 bytes parameter interface and 16 bytes input
and output process data is transferred (ASI slaves 1-31)
0xF2,0x3F (in GSD file)
KL6801 KL6801 0xB5 (in GSD file)
0xF2 (alternatively)
KL8001 KL8001 0xBB (in GSD file)
0xF5 (alternatively)

Table of Contents