Diagnostics and error handling
BK3xx0 65Version: 4.3.0
DP standard diagnostic data
Offset Meaning
0x00.0 StationNonExistent: slave did not reply to the last telegram
0x00.1 StationNotReady: slave still processing the Set_Prm / Chk_Cfg telegram
0x00.2 CfgFault: slave signaling a configuration error
0x00.3 ExtDiag: extended DiagData available and valid
0x00.4 NotSupported: slave does not support a feature requested via Set_Prm or Global_Control
0x00.5 InvalidSlaveResponse: slave response not DP-compatible
0x00.6 PrmFault: slave reports a paramétrisation error
0x00.7 MasterLock: slave currently exchanging data with another master
0x01.0 PrmReq: re-parameterize and reconfigure slave
0x01.1 StatDiag: slave signaling static diagnosis / DPV1 slave application not yet ready for data
exchange
0x01.2 PROFIBUS DP slave
0x01.3 WdOn: DP watchdog on
0x01.4 FreezeMode: DP slave in freeze mode
0x01.5 SyncMode: DP slave in sync mode
0x01.6 reserved
0x01.7 Deactivated: DP slave has been deactivated
0x02.0 reserved
0x02.1 reserved
0x02.2 reserved
0x02.3 reserved
0x02.4 reserved
0x02.5 reserved
0x02.6 reserved
0x02.7 ExtDiagOverflow: too much extended data present
0x03 MasterAdd: station address of master with which slave is exchanging data
0x04,0x05 IdentNumber
from 0x06 Device-specific diagnostic data (extended DiagData)
Device-specific diagnostic data (DPV1 status message)
The meaning of the first 4 bytes of the DPV1 status message is specified by the DPV1 standard, while the
bytes that follow are manufacturer-specific.