EasyManuals Logo
Home>Bryan Boilers>Boiler>RV Series

Bryan Boilers RV Series User Manual

Bryan Boilers RV Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
1.8.15 QUICK SELECTION FOR VENT SIZING CHARTS
GENERAL
These charts were generated using the
procedure described in Chapter 26 of the
ASHRAE Equipment Handbook (1979). The
results are consistent with those of the National
Fuel Gas Code.The responsibility for assurance
of such compliance is that of the system designer
and/or the system installer. All sizing and
installation must be checked against such local
requirements.
The sizing herein is applicable to vent systems
utilizing double wall listed Type B vent as well as
single wall insulated
vent with insulation
equivalent to double wall insulating value.
This sizing procedure is not applicable to vent
systems utilizing single wall uninsulated vents or
vent connectors.
The sizing information given herein is intended as
a general recommendation only. Vent sizing and
installation must comply with local codes.
RECTANGULAR VENTS
Vent systems may be rectangular as well as
circular. Table 1.8.15F has been provided to give
the circular equivalent of a rectangular duct.
These equivalent values account for the higher
pressure drop per cross sectional area for
rectangular ducts.
STEP 1: EQUIVALENT INPUT - DRAFT
CONTROL FACTOR
Determine the boiler (system) Draft Control
Factor, F
1
, from Table 1.8.15A.
Determine the boiler (or total system) input in
MBH. This is done by dividing the boiler (or total
system) input in Btu/hr by 1000.
Multiply the total input times factor F
1
.
The equivalent input, I, (without altitude
correction) is then: I = MBH x F
1
eq. 15A
TABLE 1.8.15A: DRAFT CONTROL FACTOR
F
1
Multiply factor times input in MBH
Boiler Type Factor, F
1
Atmospheric with Draft Hood 1.000
Atmospheric with Barometric 0.741
Forced Draft Gas or Oil 0.602
STEP 2: EQUIVALENT INPUT - ALTITUDE
FACTOR
Determine the boiler (system) Altitude Correction
Factor, F
2
, from Table 1.8.15B.
Multiply the boiler (or total system) input times
factors, F
2
and F
1
for the equivalent input.
The altitude correction factor, F
2
for atmospheric
boilers is equal to 1, because their inputs are
already derated for altitude.
The equivalent input, I, with corrections for
altitude is: I = MBH x F
1
x F
2
eq. 15B

Other manuals for Bryan Boilers RV Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryan Boilers RV Series and is the answer not in the manual?

Bryan Boilers RV Series Specifications

General IconGeneral
BrandBryan Boilers
ModelRV Series
CategoryBoiler
LanguageEnglish

Related product manuals