Model 70200
Universal Oil
Primary Control
Installation and
Operating Instructions
For Use By Qualified Service Technicians Only
It is important that the installation of the oil burner,
piping and fittings, safety devices, controls, electrical
wiring and equipment be done in accordance with
national and/or local regulations of the authorities
having jurisdiction over such installation.
126 Bailey Rd North Haven, CT 06473
Ph 203-680-9401 Fx 203-680-9403
Tech Support 800-989-2275 carlincombustion.com
©
Copyright 2023 — Carlin Combustion Technology
Carlin Combustion Technology
• Universal Replacement – for Carlin,
Beckett, Honeywell and ICM Controls
• Includes patented Smart Ignition
feature
• On-Board LCD Screen – no special
tool needed
• Optimized for performance with all
fuel blends, including B100
• Fully Programmable Settings
• 32 Cycle Fault History
• Alarm Contacts
• Communications Port
• Serviceman Reset Protection
• Blocked Vent Protection
• Built-in Pump Prime
• Recessed Spade Connectors
• Provides CAD Cell Reading in OHMS
Power input
(red/white wire) ................................ 120 VAC, 60 HZ, 9 VA
Limit circuit input
(black wire) .............................................. 120 VAC, 60 HZ
Motor load
(orange wire) .........10 FLA / 60 LRA (reduce by valve load)
Ignitor load
(blue wire) .................................... 120 VAC, 60 HZ, 500 VA
Valve load
(violet wire) .......................................... 120 VAC, 60 HZ, 2A
Vent load ................................................................. 0.1 amp
Line heater ................................................................ 1 amp
Alarm contacts (dry contacts)....................24V, AC/DC, 2A
Operating temperature limits ..................+32°F to +140°F
Storage temperature limits ...................... -40°F to +185°F
Thermostat anticipator current .......................... 0.1 A, AC
Agencies .............................. UL recognized (US & Canada)
Patent No. 10,529,191