Table 3 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
FURNACE
INPUT
(BTUH)
TWO HORIZONTAL DUCTS
(1 SQ. IN./2,000 BTUH)
(1,100 SQ. MM/KW)
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH)
(734 SQ. MM/KW)
TWO OPENINGS OR
VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH)
(550 SQ. MM/KW)
Free Area of
Opening and
Duct
Sq. In (Sq. mm)
Round Duct
In. (mm) Dia
Free Area of
Opening and
Duct
Sq. In (Sq. mm)
Round Duct
In. (mm) Dia
Free Area of
Opening and
Duct
Sq. In (mm)
Round Duct
In. (mm) Dia.
40,000* 20 (12904) 5 (127) 14 (8696) 5 (127) 10 (6452) 4 (102)
60,000 30 (19355) 6 (152) 20 (13043) 5 (127) 15 (9678) 5 (127)
80,000 40 (25807) 7 (178) 27 (17391) 6 (152) 20 (12904) 5 (127)
100,000 50 (32258) 8 (203) 34 (21739) 7 (178) 25 (16130) 6 (152)
120,000 60 (38709) 9 (229) 40 (26087) 7 (178) 30 (19355) 6 (152)
140,000* 70 (45161) 10 (254) 47 (30435) 8 (203) 35 (22581) 7 (178)
*Not all families have these models.
EXAMPLES: Determining Free Area
FURNACE WATER HEATER TOTAL INPUT
100,000 + 30,000 = (130,000 divided by 4,000) = 32.5 Sq. In. for each two Vertical Ducts or Openings
60,000 + 40,000 = (100,000 divided by 3,000) = 33.3 Sq. In. for each Single Duct or Opening
80,000 + 30,000 = (110,000 divided by 2,000) = 55.0 Sq. In. for each two Horizontal Ducts
Table 4 – Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
30 40 50 40 60 80 100 120 140
SpaceVolumeFt
3
(M
3
)
0.60
1,050
(29.7)
1,400
(39.6)
1,750
(49.5)
1,400
(39.6)
1,500
(42.5)
2,000
(56.6)
2,500
(70.8)
3,000
(84.9)
3,500
(99.1)
0.50
1,260
(35.6)
1,680
(47.5)
2,100
(59.4)
1,680
(47.5)
1,800
(51.0)
2,400
(67.9)
3,000
(84.9)
3,600
(101.9)
4,200
(118.9)
0.40
1,575
(44.5)
2,100
(59.4)
2,625
(74.3)
2,100
(59.4)
2,250
(63.7)
3,000
(84.9)
3,750
(106.1)
4,500
(127.3)
5,250
(148.6)
0.30
2,100
(59.4)
2,800
(79.2)
3,500
(99.1)
2,800
(79.2)
3,000
(84.9)
4,000
(113.2)
5,000
(141.5)
6,000
(169.8)
7,000
(198.1)
0.20
3,150
(89.1)
4,200
(118.9)
5,250
(148.6)
4,200
(118.9)
4,500
(127.3)
6,000
(169.8)
7,500
(212.2)
9,000
(254.6)
10,500
(297.1)
0.10
6,300
(178.0)
8,400
(237.8)
10,500
(297.3)
8,400
(237.8)
9,000
(254.6)
12,000
(339.5)
15,000
(424.4)
18,000
(509.2)
21,000
(594.1)
0.00 NP NP NP NP NP NP NP NP NP
NP = Not Permitted