Combination
Heating/Cooling
Units
INDEX
Page
SAFETY
CONSIDERATIONS.
1
INSTALLATION
.1-16
Step
1
Provide
Unit
Support
.
1
ROOF
CURB
SLAB
MOUNT
Step
2
Field
Fabricate
Ductwork.
1
Step
3
Rig
and
Place
Unit.
1
POSITIONING
Step
4
Install
Flue
Hood
.
3
Step
5
Trap
Condensate
Drain
.
3
Step
6
Install
Gas
Piping.
3
Step
7
Make
Electrical
Connections.
3
FIELD
POWER
SUPPLY
FIELD
CONTROL
WIRING
HEAT
ANTICIPATOR
SETTINGS
Step
8
Make
Outdoor
Air
Inlet
Adjust¬
ments
and
Install
Outdoor
Air
Hood.
10
OPTIONAL
OUTDOOR
AIR
DAMPER
OPTIONAL
ECONOMIZER
WAmmo:
power
switch
mm
to
Etectrica*
s
illl
f§§|
||
ill
111
INSTALLATION
NOTE:
004,005,006
size
units
in
California
require
the
installation
of
an
accessory
NOx
baffle.
Refer
to
Accessory
NOx
Baffle
Installation
Instructions
for
details.
Step
1
Provide
Unit
Support
ROOF
CURB
(Downshot
Units
Only)
Assemble
and
install
accessory
roof
curb
in
accordance
with
instructions
shipped
with
curb.
Curb
details
and
information
required
to
field
fabricate
a
roof
curb
are
shown
in
Fig.
1.
Install
insulation,
cant
strips,
roofing
and
flashing
as
shown.
Ductwork
must
be
attached
to
curb.
Step
9
Adjust
Evaporator
Fan
Speed.
16
START-UP.16,17
SERVICE.18-22
SAFETY
CONSIDERATIONS
Installation
and
servicing
of
air
conditioning
equipment
can
be
hazardous
due
to
system
pressure
and
electrical
components.
Only
trained
and
quali¬
fied
service
personnel
should
install,
repair
or
service
air
conditioning
equipment.
Untrained
personnel
can
perform
basic
mainte¬
nance
functions
of
cleaning
coils
and
filters
and
replacing
filters.
All
other
operations
should
be
per¬
formed
by
trained
service
personnel.
When
working
on
air
conditioning
equipment,
observe
precautions
in
the
literature,
tags
and
labels
attached
to
the
unit
and
other
safety
precautions
that
may
apply.
Follow
all
safety
codes.
Wear
safety
glasses
and
work
gloves.
Use
quenching
cloth
for
unbrazing
operations.
Have
fire
extinguishers
available
for
all
brazing
operations.
Curb
should
be
level.
Unit
leveling
tolerance
is
1/16
in.
per
linear
foot
in
any
direction.
This
is
necessary
for
unit
drain
to
function
properly.
Refer
to
Accessory
Roof
Curb
Installation
Instructions
for
additional
information
as
required.
SLAB
MOUNT(Horizontal
Units
Only)
Provide
a
level
concrete
slab
that
extends
a
minimum
of
6
in.
beyond
unit
cabinet.
The
slab
should
be
8
in.
thick
with
4
in.
above
grade.
Install
a
gravel
apron
in
front
of
condenser
air
inlet
to
prevent
grass
and
foliage
from
obstructing
airflow.
Trap
condensate
drai.n.
Allow
for
trap
when
pouring
slab.
Step
2
Field
Fabricate
Ductwork
On
downshot
units
secure
all
ducts
to
roof
curb
and
building
structure.
lHiiH
Insulate
and
weatherproof
all
external
duct¬
work,
joints
and
roof
openings
with
flashing
and
mastic
in
accordance
with
applicable
codes.
Ducts
passing
through
an
unconditioned
space
must
be
insulated
and
covered
with
a
vapor
barrier.
A
minimum
clearance
is
not
required
around
ductwork.
Cabinet
return
air
static
shall
not
exceed
-.35
in.
wg
with
economizer
or
-.45
in.
wg
without
economizer.
Step
3
Rig
and
Place
Unit
Inspect
unit
for
transportation
damage.
File
any
claim
with
trans¬
portation
agency.
Keep
upright
and
do
not
drop.
Carrier
Corporation
1984
Form
48H.L-7SI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 48HDT004 and is the answer not in the manual?

Carrier 48HDT004 Specifications

General IconGeneral
BrandCarrier
Model48HDT004
CategoryAir Conditioner
LanguageEnglish

Related product manuals