Table
1
Physical
Data
UNIT
SIZE
50CD/CH008
OPERATING
WEIGHT
(lb)
Unit
730
With
Economizer*
790
Roof
Curb*
14
in.
120
COMPRESSOR
No.
...Type
1
BRE2
Copeland
Oil
(oz)
124
REFRIGERANT
(Capillary
Control)
R-22
Charge
(lb)
105
CONDENSER
COIL
Copper
Tubes,
Aluminum
Fins
Rows
2
Fins/in.
13
9
Total
Face
Area
(sq
ft)
15
6
CONDENSER
AIR
FAN
Nominal
Cfm
4100
No.
...Diameter
(in.)
1
22
Motor
Hp
(1075
Rpm)
1/2
Hp
EVAPORATOR
COIL
Copper
Tubes,
Aluminum
Fins
Rows
3
Fins/in.
13
9
Total
Face
Area
(sq
ft)
8
2
EVAPORATOR
AIR
FAN
Quantity...Size
(in
)
1
12x9
Nominal
Cfm
3000
Minimum
and
Maximum
Cfm
(Standard
Motor)
2250
-
3650
(Optional
Motor)
2250
-
3750
Rpm
Range
Maximum
Allowable
Rpm
Motor
Pulley
Pitch
Diameter
(in.)
Fan
Pulley
Pitch
Diameter
(in
)
Belt
No.
...Type
Speed
Change
per
Full
Turn
of
652
-
924
924
2
4-3
4
12
7
1
A51
54
Moveable
Pulley
Flange
(Rpm)
Moveable
Pulley
Maximum
Full
Turns
from
Closed
Position
Factory
Setting
Full
Turns
Open
3
Factory
Speed
Setting
(Rpm)
760
Motor
Hp
(Service
Factor)
Standard
1
Hp
(1
4)
Optional
1
5
Hp
(1
3)
HIGH-PRESSURE
SWITCH
Cutout
(psig)
426
±
7
Reset
(psig)
320
±
20
LOW-PRESSURE
SWITCH
(Liquid
Line)
Cutout
(psig)
27
±
4
Reset
(psig)
67
±
7
OUTDOOR
AIR
INLET
SCREENS*
Economizer,
No
.
Size
(in
)
2
19x31x1/2
None
on
50CH008
RETURN
AIR
FILTERS*
(Type)
Disposable
None
on
50CH008
No.
...Size
(in.)
2
16
x
20
x
1
2
20
x
20
x
1
*50CD008
only
Accessory
Roof
Curb
(50CD008)
See
Fig.
2.
Assemble
and
install
in
accordance
with
instructions
shipped
with
curb.
Install
insulation,
cant
strips,
roofing
and
flashing
as
required.
Ductwork
must
be
attached
to
curb.
Unit
gasketing
to
roof
curb
is
critical
for
water
integrity.
Make
sure
that
gasketing
material
shipped
with
the
roof
curb
has
been
properly
installed
as
indicated
in
Fig.
2.
Roof
Mount
Check
building
codes
for
weight
distribution
requirements.
Table
1
shows
unit
weight.
Slab
Mount
(50CH008)
Provide
a
level
con¬
crete
slab
the
same
width
as
unit
that
extends
to
ends
of
base
rails
only.
The
slab
should
be
8
in.
thick
with
4
in.
above
grade.
Install
a
gravel
apron
in
front
of
outdoor
air
inlet
to
prevent
grass
and
foliage
from
obstructing
airflow.
Allow
a
minimum
of
6
in.
under
outdoor
coil
for
condensate
drainage.
In
areas
where
prolonged
sub-freezing
temperatures
or
heavy
snow
occur,
increase
clearance
to
12
in.
mini¬
mum,
18
in.
maximum.
Positioning
Position
unit
to
prevent
snowdrifts
from
blocking
condenser
coil
and
outdoor
air
intake
(50CD008).
Provide
clearance
around
and
above
unit
for
airflow,
safety
and
service
access.
Do
not
install
unit
in
an
indoor
location.
Do
not
locate
unit
air
inlets
near
exhaust
vents
or
other
sources
of
contaminated
air.
Although
unit
is
weatherproof,
guard
against
water
from
higher
level
runoff
and
overhangs.
©