1-1
Cisco MDS 9250i Multiservice Fabric Switch Hardware Installation Guide
OL-29583-01
APPENDIX
1
Rack Installation
This appendix provides information on the rack installation and includes the following sections:
Rack Requirements, page 1-1
Rack-Mounting Guidelines, page 1-2
Installing the Cisco MDS 9250i Switch in a Rack, page 1-6
Rack Requirements
This section provides the requirements for the following type of racks, assuming an external ambient air
temperature range of 32 to 104
o
F (0 to 40
o
C):
Cisco MDS 9250i chassis
Standard open racks
Two-post Telco racks
General Requirements for Racks
The rack must be one of the following types:
Standard 19-inch four-post EIA rack, with mounting rails that conform to English universal hole
spacing per section 1 of ANSI/EIA-310-D-1992. See the “Standard Open Rack Requirements”
section on page 1-2 and the “Standard Open Rack Requirements” section on page 1-2.
Standard two-post telco rack, with mounting rails that conform to English universal hole spacing per
section 1 of ANSI/EIA-310-D-1992.
Rack Requirements for Cisco MDS 9250i Chassis
The rack must also meet the following requirements:
The minimum vertical rack space per chassis is 1.75 in. (4.4 cm).
The width between the mounting rails must be at least 17.75 in. (45.1 cm). For four-post EIA racks,
this is the distance between the two front rails and rear rails.

Other manuals for Cisco MDS 9000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco MDS 9000 Series and is the answer not in the manual?

Cisco MDS 9000 Series Specifications

General IconGeneral
BrandCisco
ModelMDS 9000 Series
CategorySwitch
LanguageEnglish

Related product manuals