ID2-XY 160M+MC2-Y 160T
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
INDOOR
AIRFLOW (CMH)
OUTDOOR
DB(°C)
TC:TOTAL CAPACITY IN KILOWATTS (KW) PI:TOTAL POWER IN KILOWATTS (KW)
Indoor Conditions (DB °C ) Indoor Conditions (DB °C )
16.0 20.0 22.0 24.0 16.0 20.0 22.0 24.0
1820
-15.0 12.81 12.68 12.63 12.56 5.02 5.18 5.16 5.21
-10.0 13.68 13.54 13.49 13.41 5.35 5.53 5.50 5.56
-7.0 14.33 14.19 14.13 14.05 5.69 5.88 5.85 5.91
-5.6 14.59 14.45 14.39 14.30 5.61 5.72 5.77 5.82
-2.8 14.86 14.68 14.59 14.51 5.48 5.58 5.63 5.68
0.0 14.91 14.74 14.65 14.54 5.35 5.45 5.50 5.54
2.8 15.52 15.32 15.20 15.12 5.28 5.37 5.41 5.46
5.6 16.62 16.42 16.31 16.19 5.20 5.29 5.33 5.37
7.0 17.87 17.65 17.33 17.21 5.18 5.23 5.30 5.34
11.1 18.55 18.29 18.17 18.06 5.02 5.10 5.14 5.18
13.9 19.13 18.87 18.75 18.61 4.92 4.99 5.03 5.06
16.7 19.74 19.45 19.30 19.16 4.82 4.89 4.92 4.95
18.0 20.03 19.74 19.59 19.45 4.77 4.84 4.87 4.90
2210
-15.0 13.09 12.94 12.89 12.81 5.06 5.23 5.21 5.25
-10.0 13.98 13.82 13.76 13.68 5.40 5.58 5.56 5.60
-7.0 14.65 14.48 14.42 14.33 5.74 5.93 5.91 5.96
-5.6 14.91 14.74 14.68 14.59 5.66 5.77 5.82 5.88
-2.8 15.15 14.97 14.88 14.80 5.53 5.64 5.69 5.74
0.0 15.20 15.03 14.94 14.83 5.40 5.50 5.55 5.60
2.8 15.81 15.61 15.52 15.41 5.33 5.42 5.46 5.51
5.6 16.97 16.74 16.62 16.54 5.25 5.34 5.38 5.42
7.0 18.25 18.00 17.68 17.56 5.22 5.28 5.35 5.39
11.1 18.90 18.66 18.52 18.40 5.07 5.15 5.19 5.23
13.9 19.51 19.25 19.10 18.98 4.97 5.04 5.08 5.11
16.7 20.12 19.83 19.68 19.54 4.87 4.93 4.97 5.00
18.0 20.41 20.12 19.97 19.83 4.82 4.88 4.91 4.95
2600
-15.0 13.22 13.07 13.02 12.94 5.11 5.28 5.25 5.31
-10.0 14.12 13.96 13.90 13.82 5.46 5.63 5.60 5.66
-7.0 14.79 14.62 14.57 14.48 5.80 5.99 5.96 6.01
-5.6 15.06 14.88 14.83 14.74 5.72 5.82 5.88 5.93
-2.8 15.29 15.12 15.03 14.94 5.59 5.69 5.74 5.79
0.0 15.38 15.17 15.09 14.97 5.46 5.55 5.60 5.65
2.8 15.99 15.75 15.67 15.55 5.38 5.47 5.52 5.56
5.6 17.12 16.92 16.80 16.68 5.30 5.39 5.43 5.48
7.0 18.39 18.17 17.82 17.71 5.27 5.33 5.40 5.44
11.1 19.10 18.84 18.69 18.58 5.12 5.20 5.24 5.28
13.9 19.71 19.42 19.30 19.16 5.02 5.09 5.13 5.16
16.7 20.32 20.03 19.88 19.74 4.91 4.98 5.02 5.05
18.0 20.61 20.32 20.15 20.00 4.86 4.93 4.96 4.99
Note: The table shows the case where the operation frequency of a compressor is fixed.

Other manuals for CLIVET MC2-Y 140T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET MC2-Y 140T and is the answer not in the manual?

CLIVET MC2-Y 140T Specifications

General IconGeneral
BrandCLIVET
ModelMC2-Y 140T
CategoryAir Conditioner
LanguageEnglish

Related product manuals