30
Configuration
4.3 DIP Switch settings on main board
SW1_1
[0_]
1 2
Cooling mode temperature compensation:
0°C
[1_]
Cooling mode temperature compensation:
2°C
SW1_2
[_0]
ON
1 2
EEV in position 96 (step) waiting in heating
mode
[_1]
1 2
EEV in position 72 (step) waiting in heating
mode
SW2
[00]
Factory settings
SW3_1
[0_]
1 2
Reserved
[1_]
ON
1 2
Indoor unit address deletion
SW3_2
[_0]
Reserved
SW4
[00]
When the set temperature is reached
in heating mode, the fan operates on
a 4-minute off / 1-minute on cycle.
[01]
ON
1 2
When the set temperature is reached in
heating mode, the fan operates on an
8-minute off / 1-minute on cycle.
[10]
1 2
When the set temperature is reached
in heating mode, the fan operates on
a 12-minute off / 1-minute on cycle.
[11]
ON
1 2
When the set temperature is reached
in heating mode, the fan operates on
a 16-minute off / 1-minute on cycle.
SW5
[00]
In heating mode, the fan does not operate
when the temperature midpoint of the
internal heat exchanger is 15°C or lower.
[01]
1 2
In heating mode, the fan does not operate
when the temperature midpoint of the
internal heat exchanger is 20°C or lower.
[10]
1 2
In heating mode, the fan does not operate
when the temperature midpoint of the
internal heat exchanger is 24°C or lower.
[11]
1 2
In heating mode, the fan does not operate
when the temperature midpoint of the
internal heat exchanger is 26°C or lower.
SW6
[00]
Heating mode temperature compensation:
6°C
[01]
Heating mode temperature compensation:
2°C
[10]
ON
1 2
Heating mode temperature compensation:
4°C
[11]
Heating mode temperature compensation:
0°C
SW7
[00]
1 2
Reserved
J1
J1
Automatic restart function enabled
J1
Automatic restart function disabled
a
CAUTION
All DIP switches (including power DIP switches)
have been configured before delivery.
These settings should only be changed by
qualified maintenance personnel.
An incorrect setting of the DIP switch can
cause condensation, noise or unexpected
system malfunction.