Si18-525B Indoor Unit (RA Models)
Function 143
7.11 Inverter POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Details of the
Control
When POWERFUL button is pushed in each operation mode, the fan speed / setting
temperature will be converted to the following states in a period of twenty minutes.
In case of FTK(X)S20-35D
Ex.) : Powerful operation in cooling mode.
Operation mode Fan speed Target set temperature
COOL H tap + 50 rpm 18°C
DRY Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –2°C
HEAT H tap + 50 rpm 30°C
FAN H tap + 50 rpm
AUTO Same as cooling /
heating in Powerful
operation
The target is kept
unchanged
(R4560)
Target temp.
Fan
50rpm
Set temp.
18˚C
Powerful ON
Powerful OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
20min.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. Powerful operation is OFF.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin D-Series and is the answer not in the manual?

Daikin D-Series Specifications

General IconGeneral
HSPF RatingUp to 10.0
Cooling Capacity9, 000 - 36, 000 BTU/h
Heating Capacity9, 000 - 36, 000 BTU/h
Energy Efficiency Ratio (EER)Up to 12.5
Sound Level19 - 50 dB (Indoor), 49 - 60 dB (Outdoor)
Noise Level19 - 50 dB (Indoor), 49 - 60 dB (Outdoor)
Power Supply208/230V, 1-phase, 60Hz

Related product manuals