6 Manual RS8GL302 © Danfoss 2016-03 AK-CC 550B
Hot gas application
Defrost
Depending on the application you may choose between the fol-
lowing defrost methods:
Natural: Here the fans are kept operating during the defrost
Electric: The heating element is activated
Hotgas: Here the solenoid valves are controlled so that the
hotgas can ow through the evaporator
Defrost sequence
1) Pump down
2) Defrost
3) Waiting position after defrost
4) Draining (drain delay. Hotgas only)
5) Drip o
6) Delay of fan
Hot gas defrost (application 6 only)
This type of connection can be used on systems with hotgas
defrost, but only in small systems in, say, supermarkets – the
functional content has not been adapted to systems with large
charges
Relay 2 is used for suction valve
Relay 4’s change-over function can be used by the bypass valve
and/or the hotgas valve.
Must not be used together with PMLX and GPLX valves, unless a
time delay relay is installed, which ensures that the PMLX/GPLX
valve is closed completely before the hotgas is turned on.
Drip tray heating element
It is possible to control a heating element in the drip tray for
hot gas defrosting. When defrosting is commenced, the heating
element is activated. The heating element remains activated until
a set time after defrosting has ended by time or temperature.
Start of defrost
A defrost can be started in dierent ways
Interval: Defrost is started at xed time intervals, say, every
eighth hour. An interval must ALWAYS be set to
a "higher" value than the period set between two
defrostings when a schedule or network signal is used.
Refrigeration time: Defrost is started at xed refrigeration time
intervals, in other words, a low need for refrigeration will
postpone” the defrost
Schedule: Here defrost can be started at xed times of the
day and night. However, max. 6 times
Contact: Defrost is started with a contact signal on a digital input
Network: The signal for defrost is received from a system unit
via the data communication
Adaptive defrost: Here defrosting is started based on intelligent
registering of evaporator performance.
Manual: An extra defrost can be activated from the controllers
lower-most button
All the mentioned methods can be used at random – if just of
them is activated a defrost will be started.
Stop of defrost
Defrosting can be stopped by either:
• Time
Temperature (with time as safety).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CC 550B and is the answer not in the manual?

Danfoss AK-CC 550B Specifications

General IconGeneral
BrandDanfoss
ModelAK-CC 550B
CategoryController
LanguageEnglish

Related product manuals