Instruction CF-MC Master Controller
VI.UN.A1.52
Produced by Danfoss Floor Heating Hydronics 09.2005
If the Master Controller in an existing CF2-system is reset to factory
settings or replaced with another Master Controller, it is necessary to
reset all the other CF2-system components also, in order to be able to
re-install them to the reset or replaced Master Controller, CF-MC !
1. When?
Instruction CF-MC Master Controller
4
2. How?
Note: The Master Controller should only be “Reset” to factory settings if the
normal in- and uninstallation procedures can not be followed!
2.1 Resetting the Master Controller, CF-MC - g. 1:
Disconnect the 230V power supply to the Master Controller until the
power LED is OFF
Press and hold at the same time the menu selection button , the
OK button , and the output selection button
Reconnect the 230V power supply to the Master Controller and
release the three buttons when the power LED and all the output
LEDs are ON
The Master Controller is reset when all output LEDs then goes OFF