Installation Instructions
GB
Factory Setting Installer Option
Switch Function Y/N Function Y/N
1 On/O Heating - Chronoproportional, 6 CPH
2 Compressor delay disabled Compressor delay enabled
3 Not used Not used
4 4 events per day 2 events per day
DIL Switch Setting Record
It is recommended that all advanced programming and DIL
switch settings are recorded in the tables below.
Switch Description
Factory
Setting
Installer
Options
Record setting
1 Keyboard disable
Keyboard
disabled
Keyboard
disabled
2
Compressor delay timer Active
only if DIL switch enabled
2 minutes
3,4 or 5
minutes
3 Fan run-on after cooling timer O
30, 60 or
90 seconds
4 Heat/Cool deadband setting 2°C 1, 3 or 5°C
5 Thermometer calibration o set 0 + or - 3°C
Advanced Programming Setting Record