© Danfoss | DCS (ms) | 2020.01 AN331637222900en-000101 | 1
Installation Guide
ICAD Actuators
Mechanical installation of ICAD on ICM
Included in the ICAD box:
New EPDM O-ring New PTFE ring Molycote 55 grease
1. Remove existing O-ring and PTFE ring* on the ICM adapter with your fingers.
Do not use any tool because it may damage the O-ring/PTFE ring
2. Install the new PTFE ring*
3. Apply Molycote 55 grease in groove below o-ring
4. Apply Molycote 55 grease on the EPDM O-ring
5. Install the new EPDM O-ring in groove
6. Observe that Molycote 55 grease is distributed, in the groove,
all around the ICM adapter
7. Apply a very thin film of Molycote 55 around and on the ICAD magnets
8. Turn all 3 set screws about 3 turns clockwise
and then counterclockwise back to its original
position
O-ring
PTFE ring
Groove where ICAD
set screws are fastend
This Installation guide cover installation of ICAD
•on complete new ICM top part (function module)
•on ICM top part already in operation
*If the ICM top part is new there is no need to replace PTFE ring
Clockwise Counterclockwise
ICM bonnet