DKRCC.PI.A00.C6.02 | 2
TE 5 TE 12 / TE 20 TE 55
Static superheat = 4 K / 7.2°F
For range B, the static superheat need to be adjusted
Range N: -40 − 10°C / -40 – 50°F
Range NL: -40 − -5°C / -40 – 25°F
Range NM: -40 − -15°C /-40 – 5°F
Range B: -60 − -25°C / -75 – -15°F
TE 5, TE 12
TE 20, TE 55
N, NL,NM: ~ 0.5 K / 1°F superheat
B: ~ 1.5 K / 3°F superheat
N, NL,NM: ~ 0.5 K / 1°F superheat
B: ~ 1 K / 2°F superheat
Cross reference
Rated capacity )
[kW] [TR]
Type Code no.
Orifice
no.
Old code no. R407F R407A
R448A/
R449A
R404A/
R507
R22 R134a R407C R407F R407A
R448A/
R449A
R404A/
R507
R22 R134a R407C
TE 5
067B2788 0.5 – 11 9 9 7 9 5 11 3 2.5 2.5 2 2.5 1.5 3
067B2789 01
067B2089
067B2005 )
18 18 18 14 16 11 18 5 5 5 4 4.5 3 5
067B2790 02 067B2090 28 25 25 19 25 16 25 8 7 7 5.5 7 4.5 7
067B2791 03
067B2091
067B2006 )
35 32 32 25 32 21 32 10 9 9 7 9 6 9
067B2792 04
067B2092
067B2007 )
46 42 46 35 42 28 46 13 12 13 10 12 8 13
TE 12
067B2708 05 067B2008 70 56 53 49 56 35 53 20 16 15 14 16 10 15
067B2709 06 – 95 74 70 63 74 49 74 27 21 20 18 21 14 21
067B2710 07 – 113 95 91 81 95 63 91 32 27 26 23 27 18 26
TE 20
067B2771 08
067B2172
067B2170
067B2175
141 127 123 84 127 77 116 40 36 35 24 36 22 33
067B2773 09 – 158 148 141 102 148 91 134 45 42 40 29 42 26 38
TE 55
067G2705 9B – 123 109 113 84 113 74 109 35 31 32 24 32 21 31
067G2701 10 – 172 165 155 127 169 109 162 49 47 44 36 48 31 46
067G2704 11
067G2005
067G2001
067G2011
186 183 169 137 183 120 176 53 52 48 39 52 34 50
067G2707 12 – 208 200 186 151 200 134 190 59 57 53 43 57 38 54
067G2710 13
067G2006
067G2002
067G2012
250 243 225 183 246 165 232 71 69 64 52 70 47 66
) Part of old TE 12 valve assembly. Need to change to TE 5 valve body and element for replacement
) The rated capacity is based on:
- Evaporating temperature t
e
= 4.4°C / 40°F
- Condensing temperature t
c
= 38°C / 100°F
- Refrigerant temperature ahead of valve t
l
= 37 °C / 9°F