VLT
®
5000 Series
Cable lengths, cross-sections and connectors:
Max. motor cable length, screened cable ..................................................................................................... 150 m
Max. motor cable length, unscreened cable ................................................................................................. 300 m
Max. motor cable length, screened cable VLT 5011 380-500 V .................................................................... 100 m
Max. motor cable length, screened cable VLT 5011 525-600 V
and VLT 5008, normal overload mode, 525-600 V ..........................................................................................50m
Max. brake cable length, screened cable ........................................................................................................ 20 m
Max. loadsharing cable length, screened cable ..................................... 25 m from frequency converter to DC bar.
Max. cable cross-section for motor, brake and loadsharing, see Electrical data
Max. cable cross-section for 24 V external DC supply
- VLT 5001-5027 200-240 V; VLT 5001-5102 380-500 V; VLT 5001-5062 525-600 V ................. 4 mm
2
/10 AWG
- VLT 5032-5052 200-240 V; VLT 5122-5552 380-500 V; VLT 5042-5602 525-690 V .............. 2.5 mm
2
/12 AWG
Max. cross-section for control cables ....................................................................................... 1.5 mm
2
/16 AWG
Max. cross-section for serial communication ............................................................................ 1.5 mm
2
/16 AWG
If UL/cUL is to be complied with, copper cable withtemperatureclass60/75°Cmustbeused
(VLT 5001 - 5062 380 - 500 V, 525 - 600 V and VLT 5001 - 5027 200 - 240 V).
If UL/cUL is to be complied with, copper cable with temperature class 75°C must be used
(VLT 5072 - 5552 380 - 500 V, VLT 5032 - 5052 200 - 240 V, VLT 5042 - 5602 525 - 690 V).
Connectors are for use of both copper and aluminium cables, unless other is specified.
Accuracy of display readout (parameters 009-012):
Motor current [6] 0-140% load ............................................................... Max. error: ±2.0% of rated output current
Torque % [7], -100 - 140% load ...................................................................... Max. error: ±5% of rated motor size
Output [8], power HP [9], 0-90% load ................................................................... Max. error: ±5% of rated output
Control characteristics:
Frequency range .................................................................................................................................. 0 - 1000 Hz
Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ............................................................................................................................... 3 msec.
Speed, control range (open loop) ..................................................................................... 1:100 of synchro. speed
Speed, control range (closed loop) ................................................................................. 1:1000 of synchro. speed
Speed, accuracy (open loop) ............................................................................ < 1500 rpm: max. error ± 7.5 rpm
..................................................................................................... >1500 rpm: max. error of 0.5% of actual speed
Speed, accuracy (closed loop) .......................................................................... < 1500 rpm: max. error ± 1.5 rpm
..................................................................................................... >1500 rpm: max. error of 0.1% of actual speed
Torque control accuracy (open loop) ................................................ 0- 150 rpm: max. error ±20% of rated torque
................................................................................................... 150-1500 rpm: max. error ±10% of rated torque
........................................................................................................ >1500 rpm: max. error ±20% of rated torque
Torque control accuracy (speed feedback) ............................................................. Max. error ±5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
Externals:
Enclosure (dependent on power size) ................................................................ IP 00, IP 20, IP 21, Nema 1, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ................................................................................ 93 % (IEC 68-2-3) for storage/transport
Max. relative humidity ............................................... 95 % non condensing (IEC 721-3-3; class 3K3) for operation
Aggressive environment (IEC 721 - 3 - 3) ................................................................................ Uncoated class 3C2
Aggressive environment (IEC 721 - 3 - 3) .................................................................................... Coated class3C3
Ambient temperature IP 20/Nema 1 (high overload torque 160%) .......... Max. 45°C (24-hour average max. 40°C)
Ambient temperature IP 20/Nema 1 (normal overload torque 110%) ....... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 54 (high overload torque 160%) ....................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 54 (normal overload torque 110%) .................... Max. 40°C (24-hour average max. 35°C)
Ambient temperature IP 20/54 VLT 5011 500 V ..................................... Max. 40°C (24-hour average max. 35°C)
MG.51.A9.02 - VLT is a registered Danfoss trademark
14