VLT
®
5000 Series
VLT 5000 Series protection:
Electronic motor thermal protection against overload.
Temperature monitoring of heat-sink ensures that the frequency converter cuts out if the temperature reaches 90°C
for IP 00, IP 20 and Nema 1. For IP 54, the cut-out temperature is 80°C. An overtemperature can only be reset when
the temperature of the heat-sink has fallen below 60°C.
For the units mentioned below, the limits are as follows:
- VLT 5122, 380-500 V, cuts out at 75°C and can be reset if the temperature has fallen below 60°C.
- VLT 5152, 380-500 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.
- VLT 5202, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.
- VLT 5252, 380-500 V, cuts out at 95°C and can be reset if the temperature has fallen below 65°C.
- VLT 5302, 380-500 V, cuts out at 105°C and can be reset if the temperature has fallen below 75°C.
- VLT 5352-5552, 380-500 V, cut out at 85°C and can be reset if the temperature has fallen below 60°C.
- VLT 5042-5122, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.
- VLT 5152, 525-690 V, cuts out at 80°C and can be reset if the temperature has fallen below 60°C.
- VLT 5202-5352, 525-690 V, cut out at 100°C and can be reset if the temperature has fallen below 70°C.
- VLT 5402-5602, 525-690 V, cut out at 75°C and can be reset if the temperature has fallen below 60°C.
The frequency converter is protected against short-circuiting on motor terminals U, V, W.
The frequency converter is protected against earth fault on motor terminals U, V, W.
Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate circuit voltage becomes
too high or too low.
If a motor phase is missing, the frequency converter cuts out, see parameter 234 Motor phase monitor.
If there is a mains fault, the frequency converter is able to carry out a controlled decelleration.
If a mains phase is missing, the frequency converter will cut out when a load is placed on the motor.
MG.51.A9.02 - VLT is a registered Danfoss trademark
16

Table of Contents

Other manuals for Danfoss VLT 5000 Crane Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Crane Series and is the answer not in the manual?

Danfoss VLT 5000 Crane Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Crane Series
CategoryMedia Converter
LanguageEnglish

Related product manuals