7. If the intermediate circuit voltage is higher
than the intermediate circuit voltage -2% be-
fore the brake test, discontinue the brake
check and give off a warning or alarm.
8. Brake check OK.
Description of choice:
If Off [0] is selected, this function will still monitor
whether the brake resistor and the brake IGBT short-
circuit during operation, in which case it will give off a
warning. If Warning [1] is selected, the brake resistor
and brake IGBT will be monitored with respect to short-
circuiting. In addition, on power-up it will be checked
whether the brake resistor has been disconnected.
NOTE
A warning in connection with Off [0] or
Warning [1] can only be removed by dis-
connecting the mains supply and turning
it back on, provided the fault has been
corrected. Please note that in connection
with Off [0] or Warning [1] the adjustable
frequency drive will continue even if a fault
has been found.
In the case of Trip [2], the adjustable frequency drive
will cut out while giving an alarm (trip locked) if the
brake resistor has short-circuited or been disconnec-
ted or if the brake IGBT has short-circuited.
405 Reset function (RESET MODE)
Value:
Manual reset (MANUAL RESET) [0]
Automatic reset x 1 (AUTOMATIC X 1) [1]
Automatic reset x 2 (AUTOMATIC X 2) [2]
Automatic reset x 3 (AUTOMATIC X 3) [3]
Automatic reset x 4 (AUTOMATIC X 4) [4]
Automatic reset x 5 (AUTOMATIC X 5) [5]
Automatic reset x 6 (AUTOMATIC X 6) [6]
Automatic reset x 7 (AUTOMATIC X 7) [7]
Automatic reset x 8 (AUTOMATIC X 8) [8]
Automatic reset x 9 (AUTOMATIC X 9) [9]
Automatic reset x 10 (AUTOMATIC X 10) [10]
Function:
This parameter makes it possible to select the reset
function desired after tripping.
After reset, the adjustable frequency drive can be re-
started.
Description of choice:
If Manual reset [0] is selected, reset must be effected
via the [RESET] key or via the digital inputs.
If the adjustable frequency drive is to carry out an au-
tomatic reset (1-10 times) after tripping, select data
value [1]-[10].
NOTE
The internal AUTOMATIC RESET coun-
ter is reset 10 minutes after the first AU-
TOMATIC RESET has occurred.
Warning: The motor may start without
warning.
406 Automatic restart time
(AUT RESTART TIME)
Value:
0 - 10 sec.
5 sec.
Function:
This parameter allows setting of the time from tripping
until the automatic reset function begins.
It is assumed that automatic reset has been selected
in parameter 405.
Description of choice:
Set the desired time.
407 Mains failure
(MAINS FAILURE)
Value:
No function (NO FUNCTION) [0]
Controlled ramp-down
(CONTROL RAMP DOWN) [1]
Controlled ramp-down and trip
(CTRL. RAMP DOWN-TRIP) [2]
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 127
Programming

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals