Free a data-log if there is a trip and release it when
resetting the adjustable frequency drive. Data-logging
is active when the motor is running.
Digital inputs, parameter 606:
The value for the digital inputs is given as a decimal
figure within the range of 0-255.
The data-log number is stated in square brackets: [1]
175ZA449.10
63.0 %
EXT. REFERENCE, %
606 DATALOG:DIGITALINPUT
[0] 40
Control word, parameter 607:
The value for the control word is given as a decimal
figure within the range of 0-65535.
Status word, parameter 608:
The value for the bus status word is given as a decimal
figure within the range of 0-65535.
Reference, parameter 609:
The value of the reference is stated as a % in the in-
terval 0 - 100%.
Feedback, parameter 610:
The value is stated as the parameterised feedback.
Output frequency, parameter 611:
The value of the motor frequency is stated as a fre-
quency in the interval 0.0 - 999.9 Hz.
Output voltage, parameter 612:
The value of the motor voltage is stated as Volts in the
interval 50 - 1000 V.
Output current, parameter 613:
The value for the motor current is stated as Amps in
the interval 0.0 - 999.9 A.
DC link voltage, parameter 614:
The value of the DC link voltage is stated as Volts in
the interval 0.0 - 999.9 V.
615 Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10] Error code 0 - 44
Function:
This parameter makes it possible to see the reason
why a trip occurs.
10 (0-10) log values are stored.
The lowest log number (1) contains the latest/most re-
cently saved data value; the highest log number (10)
contains the oldest data value.
Description of choice:
Given as a number code in which the trip number re-
fers to an alarm code that can be seen in the table in
section Warnings and Alarms.
Reset the fault log after manual initialization.
616 Fault log: Time
(F.LOG: TIME)
Value:
[Index 1 - 10]
Function:
This parameter makes it possible to see the total num-
ber of operating hours before the trip occurred. 10
(0-10) log values are stored.
The lowest log number [1] contains the latest/most re-
cently saved data value, while the highest log number
[10] contains the oldest data value.
Description of choice:
Read out as an option.
Indication range: 0.0 - 9999.9.
Reset the fault log after manual initialisation.
617 Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10]
Function:
This parameter makes it possible to see at what cur-
rent or voltage a given trip occurred.
Description of choice:
Read out as one value.
Indication range: 0.0 - 999.9.
Reset the fault log after manual initialisation.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
150 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals