This key can only be used if parameter 002 has
been set to Local operation [1] and parameter
013 to LCP control [3].
Description of choice:
If Disable [0] is selected, the [FWD/REV]
key will be inactive.
See parameter 200.
017 Local reset of trip (LOCAL RESET)
Value:
Not possible (DISABLE)
[0]
✭Possible (ENABLE)
[1]
Function:
In this parameter, the reset function can be
selected/removed from the keyboard.
This key can be used when parameter 002 has been
set for Remote control [0] or Local control [1].
Description of choice:
If Disable [0] is selected in this parameter, the
[RESET] key will be inactive.
NB!:
Only select Disable [0] if an external reset signal
has been connected via the digital inputs.
018 Lock for data change
(DATA CHANGE LOCK)
Value:
✭Not locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
In this parameter, the software can "lock" the
control, which means that data changes cannot
be made via LCP (however, this is still possible
via the serial communication port).
Description of choice:
If Locked [1] is selected, data changes cannot be made.
019 Operating state at Power up, local control
(POWER UP ACTION)
Value:
Auto restart, use saved ref. (AUTO RESTART)
[0]
✭Forced stop, use saved ref. (LOCAL=STOP)
[1]
Forced stop, set ref. to 0
(LOCAL=STOP, REF=0)
[2]
Function:
Setting of the operating mode when the mains
voltage is reconnected.
This function can only be active in connection with
Local control [1] in parameter 002.
Description of choice:
Auto restart, use saved ref. [0] is selected if the unit
is to start up with the same local reference (set in
parameter 003) and the same start/stop conditions
(given via the [START/STOP] keys) that the frequency
converter had before it was switched off.
Forced stop, use saved ref. [1] is used if the
unit is to remain stopped when the mains voltage
is connected, until the [START] key is pressed.
After the start command, the local reference
used is set in parameter 003.
Forced stop, set ref. to 0 [2] is selected if the unit is to
remain stopped when the mains voltage is connected.
Local reference (parameter 003) is reset.
NB!:
In remote controlled operation (parameter
002), the start/stop condition at power up
will depend on the external control signals.
If Pulse start [2] is selected in parameter 302, the
motor will remain stopped at power-up.
027 Warning readout line
(WARNING READOUT)
Value:
✭Warning in line 1/2
[0]
Warning in line 3/4
[1]
Function:
In this parameter it is decided in which line the warning
is to appear in display mode. In programming mode
(Menu or Quick menu) the warning will appear in line
1/2 to avoid disturbance of the programming.
Description of choice:
Select the readout line.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port