Electrical installation
Conversion of analogue inputs
Current input signal to voltage input
0-20 mA 0-10 V
Connect 510 ohms resistor between input terminal 53
and 55 and adjust minimum and maximum values in pa-
rameters 309, and 310 or 54 and 55 and adjust minimum
and maximum values in parameters 312 and 313.
4-20 mA 2-10 V
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 67