Voltage [V] Minimum waiting time (minutes)
4 7 15 20 30 40
200–240 1.1–3.7 kW
(1.50–5 hp)
–5.5–45 kW
(7.5–60 hp)
–––
380–480 1.1–7.5 kW
(1.50–10 hp)
– 11–90 kW
(15–121 hp)
– – 315–1000 kW
(450–1350 hp)
400 – – – 90–315 kW
(121–450 hp)
––
500 – – – 110–355 kW
(150–500 hp)
––
525 – – – 75–315 kW
(100–450 hp)
––
525–600 1.1–7.5 kW
(1.50–10 hp)
– 11–90 kW
(15–121 hp)
–––
690 – – – 90–315 kW
(100– 350 hp)
––
525–690 – 1.1–7.5 kW
(1.50–10 hp)
11–90 kW
(15–121 hp)
–400–1400 kW
(500–1550 hp)
450–1400 kW
(600–1550 hp)
–
Table 1.1 Discharge Time, VLT
®
HVAC Drive FC 102
Voltage [V] Minimum waiting time (minutes)
4 7 15 20 40
200–240 0.25–3.7 kW
(0.34–5 hp)
–5.5–37 kW
(7.5–50 hp)
––
380–480 0.25–7.5 kW
(0.34–10 hp)
– 11–75 kW
(15–100 hp)
110–315
(150–450 hp)
355–450
(500–600 hp)
355–560
(500–750 hp)
525–600 0.75–7.5 kW
(1.0–10 hp)
– 11–75 kW
(15–100 hp)
––
525–690 – 1.5–7.5 kW
(2–10 hp)
11–75 kW
(15–100 hp)
55–400
(75–400 hp)
450–630
(600–750 hp)
450–800
(600–950 hp)
Table 1.2 Discharge Time, VLT
®
Refrigeration Drive FC 103
Voltage [V]
Minimum waiting time (minutes)
4 7 15 20 30 40
200–240 0.25–3.7 kW
(0.34–5 hp)
–5.5–45 kW
(7.5–60 hp)
–––
380–480 0.37–7.5 kW
(0.5–10 hp)
– 11–90 kW
(15–121 hp)
110–315 kW
(150–450 hp)
– 315–1000 kW
(450–1350 hp)
355–560 kW
(500–750 hp)
525–600 0.75–7.5 kW
(1–10 hp)
– 11–90 kW
(15–121 hp)
–400–1400 kW
(400–1550 hp)
–
525–690 – 1.1–7.5 kW
(1.5–10 hp)
11–90 kW
(10–100 hp)
75–400 kW
(75–400 hp)
– 450–800 kW
(450–950 hp)
Table 1.3 Discharge Time, VLT
®
AQUA Drive FC 202
Installation Instructions
Control Card VLT
®
FC Series
2
Danfoss A/S © 03/2017 All rights reserved. MI93A102