VLT
®
FCD Series
Programming, FCD
300
411 Switching frequency
(SWITCH FREQ.)
Value:
3000 - 14000 Hz
4500 Hz
Function:
The set value determines the switching frequency of the
inverter. If the switching frequency is changed, this may
help to minimise possible acoustic noise from the motor.
NB!:
The output frequency of the frequency converter
can never assume a value higher than 1/10
of the switching frequency.
Description of choice:
When the motor is running, the switching frequency
is adjusted in parameter 411 Switching frequency
until the frequency has been obtained at which
the motor is as low-noise as possible.
NB!:
The switching frequency is reduced
automatically as a function of the load.
See Temperature-Dependent Switching
Frequency under Special Conditions .
413 Overmodulation function
(OVERMODULATION)
Value:
Off (OFF)
[0]
On (ON)
[1]
Function:
This parameter allows connection of the
overmodulation function for the output voltage.
Description of choice:
Off [0] means that there is no overmodulation
of the output voltage, which means that torque
ripple on the motor shaft is avoided. This can
be a good feature, e.g. on grinding machines.
On [1] means that an output voltage can be obtained
which is greater than the mains voltage (up to 5 %).
414 Minimum feedback, FB
MIN
(MIN. FEEDBACK)
Value:
-100,000.000 - par. 415 FB
MAX
0.000
Function:
Parameter 414 Minimum feedback, FB
MIN
and 415
Maximum feedback, FB
MAX
are used to scale the
display text to make it show the feedback signal in a
process unit proportionally to the signal on the input.
Description of choice:
Setthevaluetobeshownonthedisplayasthe
minimum feedback signal value on the selected
feedback input (parameters 308/314 Analogue inputs).
415 Maximum feedback, FB
MAX
(MAX. FEEDBACK)
Value:
FB
MIN
- 100,000.000
1500.000
Function:
See description of parameter 414 Minimum
feedback, FB
MIN
.
Description of choice:
Setthevaluetobeshownonthedisplaywhenthe
maximum feedback has been obtained on the selected
feedback input (parameter 308/314 Analogue inputs).
416 Process units
(REF/FEEDB. UNIT)
Value:
No unit (NO UNIT)
[0]
%(%)
[1]
ppm (PPM)
[2]
rpm (RPM)
[3]
bar (BAR)
[4]
Cycles/min (CYCLE/MI)
[5]
Pulses/s (PULSE/S)
[6]
Units/s (UNITS/S)
[7]
Units/min. (UNITS/MI)
[8]
Units/h (UNITS/H)
[9]
°C (°C)
[10]
Pa (PA)
[11]
l/s (L/S)
[12]
m
3
/s (M
3
/S)
[13]
l/min. (L/M)
[14]
m
3
/min. (M
3
/MIN)
[15]
l/h (L/H)
[16]
m
3
/h (M
3
/H)
[17]
Kg/s (KG/S)
[18]
Kg/min. (KG/MIN)
[19]
Kg/hour (KG/H)
[20]
Tons/min. (T/MIN)
[21]
Tons/hour (T/H)
[22]
Metres (M)
[23]
Nm (NM)
[24]
m/s (M/S)
[25]
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
67

Table of Contents

Other manuals for Danfoss VLT FCD 322

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 322 and is the answer not in the manual?

Danfoss VLT FCD 322 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 322
CategoryDC Drives
LanguageEnglish

Related product manuals