EasyManuals Logo
Home>Danfoss>DC Drives>VLT FCD 322

Danfoss VLT FCD 322 User Manual

Danfoss VLT FCD 322
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
VLT
®
FCD Series
Programming, FCD
300
is selected on two terminals simultaneously, the
two signals will be added together.
Use the overview below to determine which
terminal is to be used and which parameters
are to be programmed.
Feedback type Terminal Parameters
Pulse 29, 33 305, 307, 327, 328
Voltage 53 308, 309, 310
Current 60 314, 315, 316
A correction can be made for loss of voltage
in long signal cables when a transmitter with a
voltage output is used. Thi
s is done in parameter
group 300 Min./Max scaling.
Parameters 414/415 Minimum/Maximum feedback
must also be preset to a value in the process unit
corresponding to
the minimum and maximum scaling
values for signals that are connected to the terminal.
R
eference
In parameter 205 Maximum reference, Ref
MAX
it is
possible to pre
set a maximum reference that scales
the sum of all references, i.e. the resulting reference.
The minimum reference in parameter 204 is
an expressi
on of the minimum value that the
resulting reference can assume.
All references will be added together and the sum
will be the
reference against which regulation will
take place. It is possible to limit the reference range
to a range that is smaller than the feedback range.
This c
an be an advantage if you want to avoid
an unintentional change to an external reference
making the sum of the references move too far
aw
ay from the optimal reference. The reference
range cannot exceed the feedback range.
If preset references are desired, they are preset
i
n parameters 215 to 218 Preset reference.
See description Re ference Function and
Handling of References.
If a current signal is used as the feedback signal,
it will only be possible to use voltage as an
analogue reference. Use the overview below to
determine which terminal is to be used and which
parameters are to be programmed.
Reference type Terminal Parameters
Pulse 29, 33 305, 307, 327, 328
Voltage 53 308, 309, 310
Current 60 314, 315, 316
Preset
references
215-218
Bus reference 68+69
Note that the bus reference can only be preset
via serial communication.
NB!:
It is best to preset terminals that are not
being used to No function [0].
D
ifferentiator gain limit
If very rapid variations occur in an application in
either the reference signal or the feedback signal,
the deviation between the reference/setpoint and
the processs actual mode will change quickly.
Thedifferentiator can then become too dominant. This
is because it is reacting to the deviation between
the reference and the processs actual mode,
and the quicker the variance changes the more
powerful the differentiators frequency contribution
becomes. The differentiators frequency contribution
can therefore be limited in such a way that both
a reasonable differentiation time for slow changes
and an appropriate frequency contribution for quick
changes can be preset. This is done using the speed
regulation in parameter 420 Speed PID Differentiator
gain limit and Process regulation in parameter 443
Process PID Differentiator gain limit.
L
owpass filter
If there is a lot of noise in the feedback signal, these
can be dampened using an integratedlowpass filter.
A suitable lowpass filter time constant is preset.
If the lowpass filter is preset to 0.1 s, the cut-off
frequency will be 10 RAD/sec, corresponding to (10 / 2
x π) = 1.6 Hz. This will mean that all currents/voltages
that vary by more than 1.6 oscillations per second
will be dampened. In other words, there will only
be regulation on the basis of a feedback signal
that varies by a frequency of less than 1.6 Hz.
The appropriate time constant is selected in Speed
Regulation in parameter 421 Speed PID lowpass
filter time and in Process Regulation in parameter
444 Process PID lowpass filter time.
I
nverse regulation
Normal regulation means that the motor speed is
increased when the reference/setpoint is greater
than the feedback signal. If it is necessary to run
inverse regulation, in which the speed is reduced
when the reference/setpoint is greater than the
feedback signal, parameter 437 PID normal/inverted
control must be programmed at Inverted .
A
nti Windup
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
69

Table of Contents

Other manuals for Danfoss VLT FCD 322

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 322 and is the answer not in the manual?

Danfoss VLT FCD 322 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 322
CategoryDC Drives
LanguageEnglish

Related product manuals