VLT
®
FCD Series
Programming, FCD
300
Example - Write a parameter value:
Parameter 202 Output frequenc y hig h limit, f
MAX
to
be changed to 100 Hz. The value must be recalled
after a mains failure, so it is written in EEPROM.
PKE = E0CA Hex - Write for parameter 202
Output frequency high limit, f
MAX
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 03E8 Hex - Data value 1000,
corresponding to 100 Hz, see conversion.
Theresponsefromtheslavetothemasterwillbe:
Example - Selection of a data value:
You wish to select kg/hour [20] in parameter 416
Process units. The value must be recalled after a
mains failure, so it is written in EEPROM.
PKE = E19F Hex - Write for parameter
416 Process units
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0014 Hex - Select data option
kg/hour [20]
Theresponsefromtheslavetothemasterwillbe:
Example - Reading a parameter value:
The value in parameter 207 Ramp up time 1 is required.
The master sends the following request:
PKE = 10CF Hex - read parameter 207
Ramp up time 1
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0000 Hex
If the value in parameter 207 Ramp-up t ime 1 is 10
sec., the response from the slave to the master will be:
Conversion:
Under the section entitled Factory Settings the
various attributes of each parameter are displayed.
As a parameter value can only be transferred
as a whole number, a conversion factor must
be used to transfer decimals.
E
xample:
Parameter 201 Output frequency, low limit f
MIN
has
a conversion factor of 0.1. If you wish to preset the
minimum frequency to 10 Hz, the value 100 must
be transferred, as a conversion factor of 0.1 means
that the value transferred is multiplied by 0.1. The
value 100 will thus be perceived as 10.0.
Conversion table
Conversion
index
Conversion
factor
73 0.1
2 100
110
01
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
Process Words
The block of process words is divided into two blocks
of 16 bi
ts, which always occur in the defined sequence.
PCD 1 PCD 2
Control telegram
(masterslave)
Control word Reference-
value
Control telegram
(slavemaster)
Status word Present outp.
frequency
MG.04.B7.02 - VLT is a registered Danfoss trademark
81

Table of Contents

Other manuals for Danfoss VLT FCD 322

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 322 and is the answer not in the manual?

Danfoss VLT FCD 322 Specifications

General IconGeneral
Protection ClassIP20
Enclosure RatingIP20
Control MethodVector control
Communication ProtocolsCANopen
ProtectionOvervoltage, Overcurrent, Short Circuit
Ambient Temperature-10 to +50 °C

Summary

Introduction to FCD 300

Software Version Information

Details the software version compatibility for the operating instructions.

Safety Warnings and Precautions

Covers high voltage, general safety rules, and preventing unintended starts.

Installation

Mechanical Installation Requirements

Covers unit dimensions, mounting options, and spacing for cooling.

Electrical Installation Best Practices

Details general practices, earthing, EMC, and ATEX compliance.

Wiring Diagrams and Terminal Connections

Provides wiring diagrams, terminal identification, and connection examples.

Programming, FCD 300

Local Control Panel (LCP 2) Operation

Explains the functions and operation of the LCP 2 unit for programming.

Parameter Setup and Navigation Methods

Details accessing and changing parameters via Menu and Quick Menu modes.

Configuration Settings and Operation Modes

Covers local/remote operation, setup configurations, and display modes.

Motor and Load Configuration Parameters

Details parameters for motor type, torque, power, and load compensation.

Input and Output Configuration

Explains settings for digital inputs, analog inputs/outputs, and pulse signals.

Special Functions and PID Control Settings

Covers brake functions, reset modes, and PID regulator configurations.

Serial Communication Protocols and Settings

Details communication protocols, telegram structure, and Modbus parameters.

All about FCD 300

Service and Diagnostics Features

Covers LED diagnostics, LCP interface, and fault logging for troubleshooting.

Warning and Alarm Messages

Provides a comprehensive list and explanation of all warning and alarm conditions.

Technical Data and Environmental Factors

Includes derating for speed/temperature, aggressive environments, and general technical specs.

Related product manuals