Chapter 11 Summary of Parameter SettingsMS300
257
Pr.
Explanation
Settings
Default
14-69
IGBT Temperature at
Malfunction 6
-3276.7–3276.7
o
C
Read only
14-70
Fault Record 7
Refer to fault record Pr.06-17Pr.06-22
0
14-71
Fault Record 8
Refer to fault record Pr.06-17Pr.06-22
0
14-72
Fault Record 9
Refer to fault record Pr.06-17Pr.06-22
0
14-73
Fault Record 10
Refer to fault record Pr.06-17Pr.06-22
0
14-74
Over-Torque Detection
Selection (Motor 3)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant
speed operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
0
14-75
Over-Torque Detection
Level (Motor 3)
10–250%
(100% corresponds to the rated current of the drive)
120
14-76
Over-Torque Detection
Time (Motor 3)
0.1–60.0 sec.
0.1
14-77
Over-Torque Detection
Selection (Motor 4)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant speed
operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
0
14-78
Over-Torque Detection
Level (Motor 4)
10–250%
(100% corresponds the rated current of the drive)
120
14-79
Over-Torque Detection
Time (Motor 4)
0.1–60.0 sec.
0.1
14-80
Electronic Thermal Relay
Selection 3 (Motor 3)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with the fan on the shaft)
2: Disable
2
14-81
Electronic Thermal Relay
Action Time 3 (Motor 3)
30.0–600.0 sec.
60.0
14-82
Electronic Thermal Relay
Selection 4 (Motor 4)
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with the fan on the shaft)
2: Disable
2
14-83
Electronic Thermal Relay
Action Time 4 (Motor 4)
30.0–600.0 sec.
60.0

Table of Contents

Other manuals for Delta VFD5A5MS43ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD5A5MS43ANSAA and is the answer not in the manual?

Delta VFD5A5MS43ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD5A5MS43ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals