Eaton 93E UPS 15-80 kVA (380/400/415 V) Installation and Operation Manual
© Eaton Corporation plc 2015. All rights reserved. Revision: 001
Document ID: 614-01975-00
130 (133)
Output voltage balance
< 2% for 100% maximum load
imbalance (linear load)
Output voltage phase displacement
< 2.5° for 100% maximum load
imbalance (linear load)
Frequency regulation
0.1 Hz free running
Synchronous to bypass
± 4 Hz (default setting)
Frequency slew rate
3 Hz per second (default setting)
Load compatibility
0.9 PF leading
0.7 PF lagging
Overload capability
110% for 60 minutes
125% for 10 minutes
150 % for 1 minutes
150% for 500 milliseconds
Short-circuit current
2 x In for 0…100 ms
1.5 x In for 100…160 ms