EasyManuals Logo
Home>Eaton>Cables and connectors>QD5

Eaton QD5 Installation Instruction

Eaton QD5
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
General
Eatons Cooper Power™ series 200 A, 35
kV insulated protective cap meets the full
requirements of IEEE Std 386™-2006 standard–
Separable Insulated Connector Systems, and
provides an insulated, fully shielded submersible
cover for an energized 35 kV Class loadbreak
interface. The molded peroxide-cured EPDM
semi-conductive shield maintains ground potential
on the cap’s surface when the drain wire is
attached to a grounding lug. The protective cap is
required for temporary or permanent installation
on 21.1 kV and 21.1/36.6 kV loadbreak bushings,
portable feedthru junctions, and other accessories
having interfaces that conform to IEEE Std 386™-
2006 standard (200 A loadbreak interface No. 1,
21.1 kV and 21.1/36.6 kV).
Installation
No special tools are required. A clampstick tool is
used to place the protective cap on an exposed
bushing. Refer to Installation Instruction Sheet
S500-65-1 for details.
Production tests
Tests conducted in accordance with IEEE Std
386™-2006 standard.
AC 60 Hz 1 Minute Withstand
50 kV
Minimum Corona Voltage Level
26 kV
Tests conducted in accordance with Eaton
requirements.
Physical Inspection
Periodic Dissection
Periodic X-ray Analysis
200 A 35 kV class insulated protective
cap
Loadbreak
Connectors
CA650 087EN
Effective November 2015
Supersedes TD650001EN August 2014
COOPER POWER
SERIES

Other manuals for Eaton QD5