EasyManuals Logo
Home>Edwards>Control Unit>SIGA-CC2

Edwards SIGA-CC2 User Manual

Edwards SIGA-CC2
5 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
© 2017 United Technologies Corporation 1 / 5 P/N 387040P-EN • REV 013 • ISS 20SEP17
SIGA-CC2 Dual Input Signal Module
Installation Sheet
Description
The SIGA-CC2 Dual Input Signal Module is an addressable
device that connects one of two risers to a Class B supervised
output circuit.
When activated, the module connects the output circuit to the
Riser 1 or Riser 2 input. The input can be either 24 VDC (to
operate polarized audible and visible signal notification
appliances), or 25 or 70 VRMS (to operate audio evacuation
speakers). Typically, the Riser 1 input connects to the ALERT
channel and the Riser 2 input connects to the EVAC channel.
The module does not provide signal synchronization. To meet
UL 864 requirements for horn and strobe signal
synchronization, you must install a Genesis Signal Master
module. This module does not provide supervision of the riser;
the fire alarm panel provides this function.
The SIGA-CC2 module requires two addresses on the
signaling line circuit (SLC). Addresses are assigned
electronically. There are no address switches.
Diagnostic LEDs provide visible indication of the state of the
module through the cover plate:
Normal: Green LED flashes
Alarm/active: Red LED flashes
Personality codes
Use the personality codes described below to configure the
SIGA-CC2 module. See Table 1 for listing information.
Table 1: Personality codes
Code
Description
UL 864
CAN/ULC-
S527
EN 54-18
7
Riser selector -
supervised output
(Class B)
Personality code 7: Riser selector - supervised output
(Class B). Configures the SIGA-CC2 module as a
one - or two - input, signal power (24 VDC) or audio evacuation
(25 or 70 VRMS) riser selector. The output circuit is monitored
for open or shorted wiring. If a short exists, the control panel
inhibits the activation of the signal circuit, so the riser is not
connected to the wiring fault.
Installation
Install this device in accordance with applicable national and
local codes, ordinances, and regulations.
Notes
The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
To install the module:
1. Write the address assigned to the module on the label
provided, and then apply the label to the module. Remove
the serial number label from the module, and then attach it
to the project documentation.
2. Wire in accordance with Wiringon page 2.
3. Using the self-tapping screw provided, attach the wall
plate to the module. See Figure 1.
4. Using the four machine screws, attach the wall plate and
module to the electrical box.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Edwards SIGA-CC2 and is the answer not in the manual?

Edwards SIGA-CC2 Specifications

Power IconPower
operating voltage range15.20 to 19.95 VDC
standby current310 µA
activated current135 µA
ground fault impedance10 kΩ
output rating (24 VDC)2 A
output rating (25 VRMS audio)50 W
output rating (70 VRMS audio)35 W
circuit capacitance0.1 µF max.
Operating Environment IconOperating Environment
operating temperature32 to 120°F (0 to 49°C)
relative humidity0 to 93%, noncondensing
storage temperature range−4 to 140°F (−20 to 60°C)
Weight and Dimensions IconWeight and Dimensions
electrical box minimum size3.5 × 3.5 × 1.5 in. (85 × 85 × 38 mm)
compatible electrical box depth2-1/2 in. (64 mm)
compatible electrical box depth with dual-gang cover1-1/2 in. (38 mm)

Related product manuals