1592007201 XR10C-D GB r1.0 18.11.2015 XR10C XR10D 4/4
14.3 XR10D: 8A COMPRESSOR
Power
Supply
Line
8(3)A/250Vac
13 14 15 16 17 18 19
Comp
n.c.
11 12
3 4 5 6
HOT KEY
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.
14.4 XR10D: 20A COMPRESSOR
Power
Supply
11 12
Line
Comp
20(8)A/250Vac
15 16
3 4 5 6
HOT KEY
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.
15. DEFAULT SETTING VALUES
Label
Name
Range
Cooling
°C/°F
Heating
°C/°F
Set
Set point
LS÷US
5/41
5/41
Hy
Differential
0,125.5°C/ 1 255°F
2/4
2/4
LS
Minimum set point
-50°CSET/-58°FSET
-50/-58
-50/-58
US
Maximum set point
SET110°C/ SET 230°F
150/302
150/302
Ot
Thermostat probe
calibration
-1212°C /-120120°F
0/0
0/0
OdS
Outputs delay at start up
0÷255 min
0
0
AC
Anti-short cycle delay
0 50 min
1
0
COn
Compressor ON time with
faulty probe
0 255 min
30
0
CH
Kind of action
CL=cooling; Ht= heating
CL
Ht
CF
Temperature measurement
unit
°C °F
°C/°F
°C/°F
rES
Resolution
in=integer; dE= dec.point
dE/-
dE/-
ALc
Temperat. alarms
configuration
rE= related to set;
Ab = absolute
Ab
Ab
ALU
MAXIMUM temperature
alarm
Set110.0°C; Set÷230°F
150/302
150/302
ALL
Minimum temperature alarm
-50.0°CSet/ -58°FSet
-50/-58
-50/-58
ALd
Temperature alarm delay
0 255 min
15
5
dAO
Delay of temperature alarm
at start up
0 23h e 50’
1.0
0.3
i1P
Digital input polarity
oP=opening;CL=closing
cL
CL
i1F
Digital input configuration
EAL=extern. alarm; bAL=lock
regulation; PAL=press.
switch; dor=door switch; dEF,
Lgh=disabled; Htr= heating-
cooling
EAL
EAL
did
Digital input alarm delay
0÷255min
5
5
Nps
Number of activation of
pressure switch
0 ÷15
0
0
odc
Compressor status with
open door:
no, Fan = normal;
CPr; F_C = Compr. OFF;
no
no
PbC
Kind of probe
Ptc; ntc
ntc/Ptc
ntc/Ptc
rEL
Software release
--
4.0
4.0
Ptb
Map code
--
-
-
Hidden parameters