EasyManuals Logo
Home>Emerson>Controller>FD113

Emerson FD113 User Manual

Emerson FD113
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
FD113 Oil Pressure Safety Control
FD113 Oil Pressure Safety Control
Instruction Sheet
PA-00250
June 2013
THE FLEXIBLE CONTROL
• TheFD113OilPressureSafetyControlsensestheeffectiveoil
pressuredifferentialincompressorswithpositivedisplacementoil
pumps.Ifinadequateoilpressureexists,atimedelayisenergized.
Iftheoilpressuredoesnotrecovertosafelevelswithinthetime
delaysetting,thecompressorisshutdown.Thetimedelayallows
thecompressoradequatetimetoestablishoilpressureonstart–up
andavoidsnuisanceshutdownsonpressuredropofshortduration
duringtheruncycle.
• Maximumapplicationexibilityisassuredbyprovidingan
adjustabledifferentialpressureswitchwhichcanbeadjustedto
thecompressor’sminimumrequiredoilpressureneedsandan
adjustabletimedelaywhichallowsyoutoselectthelengthof
timethecompressorrunsbelowtheminimumpressurebefore
shutdown.Theminimumpressuresettingandtimedelayvalues
speciedbythecompressormanufacturershouldbeusedwhen
installingtheFD113control.
FEATURES
• PressureRangeadjustablefrom4to65PSID.
Timerstartpressure–timerstoppressureis3PSIDabove
timerstartpressure.
• ASPDTswitchisusedinthepressureportionofthecontrol
whichallowstheadditionofa“safelight”ifdesired.
• TimerisTime–Adjustablefrom20to150seconds.
Supplyvoltage–24to240VoltAC/DC.Timingunaffectedby
voltageorambienttemperaturevariations.
• ASPDTManualResetSwitchisusedintheTimerModule.
Upontime-out,thecompressorisstoppedandanalarmcircuit
isenergized.Torestartthecompressorandde-energizethe
alarmcircuit,theresetbuttonispushed.
• AfactoryinstalledJumperallowstheFD113tobepoweredfrom
asinglepowersource.Shouldseparatecircuitsbedesiredfor
thetimerand“Lockout”switch,theJumpercanberemoved.
SAFETY INSTRUCTIONS
1. ReadallInstructionsthoroughly.Failuretocomplycanresult
incontrolfailure,systemdamageorpersonalinjury.
2. Donotusewithammoniaoronhazardousorcorrosiveuids.
3. DonotinstallinHazardousLocations.
4. Disconnectelectricalpowerbeforeinstallation.Donotreapply
poweruntilcontrolinstallationiscomplete,wiringconnections
securedandcoverisinplace.
5. Beforemakingpressurecontrolconnections,depressurize
systemandmakecertainlinesareatatmosphericpressure.
Pilot Duty Ratings: 120/240VAC
U.L.B300 360VAMaximum
CONTROL RATINGS
INSTALLATION INSTRUCTIONS–GENERAL
1. Cover Removal—Loosencoverscrew,pullcoverforward.
2. Mounting—Mountthecontrolinaprotectedareaonthe
mountingbracketoraatsurfacewithscrewsprovided.
CAUTION:Ifotherscrewsareused,use8-32screwsthat
do notpenetrateintothecontrolmorethan1/8’’.
OilPressureSafetyControlsshouldalwaysbemounted
abovetheoillevelinthecompressorcrankcase.The
capillarytubesorpressureconnectionsshouldberouted
toallowthemtobefree–drainingtothecompressor
crankcase.Thiswillpreventoillogginginthecapillary
tubesduringlowambientconditions.
3. Capillary Tube Connections:Properinstallationof
capillarytubesand/orpressurecontrollineswillinsure
atrouble–freeinstallation.WARNING:Beforemakingany
pressurecontrolconnections,depressurizesystem.Failure
todosocancausesystemdamageorpersonalinjury.
• Ifthecontrolismountedonthecompressor,alllines
mustbesecuredtothecompressorsotheydonot
vibrateindependentlyfromthecompressor.
• Ifthecontrolismountedremotefromthecompressor
anopencoiledvibrationloop,2to3coils,2to3’’
diametershouldbeprovidedbetweenthecompressor
baseandthemovingcompressor.Thelinescoming
fromthecoilshouldbesecuredtothebaseand
compressorsothecoiltakesallthevibration.Avoid
any“violinstring”runsofcontrolcapillarytubes.
• Sharpbendsorkinksmustbeavoidedinthecapillary
orpressurelines.Donotallowthelinestoruband
abradeagainstanymovingsurface.Avoidanyexcess-
ivehandlingorreformingofthecopperlinesto
minimizeworkhardeningofthecopper.
4. Electrical ConnectionsWARNING: Beforemakingany
electricalconnections,disconnectallelectricalpower.
Checkwithavoltmeterasmorethanonesourceofpower
maybesupplied.Makecertaintheloadtoconnectedis
withintheelectricalratingofthecontrol(seeTable1).
• AllwiringshouldconformtoNationalElectricalCode
and/orlocalcodes.Use14AWG or larger copper
conductors ONLY.
• Theterminalsareofaclampdesign.Loosenthe
terminalscrewswithasmallscrewdriver,insert
approximately3/8’’strippedwireandsecurelytighten.
SPECIFICATIONS – FD113ZU/ZUK
Ambient Temperature Range –5°Fto+140°F
Pressure Range–PSID–Adjustable
Timer Energize:4to65PSIDneteffectiveoilpressureon
pressuredrop.
Timer De-energize:3PSIabovetimerenergizesettingon
pressurerise.
Timer
Voltage:24to240voltsACorDC
Timing:20to150seconds–Adjustable
Maximum Over Pressure:Duringinstallationandservice,the
control’spowerelementshouldnotbeexposedtopressures
exceeding330PSIG.
NEMA CLASS I – Mount the control body in an area
protected from the weather, water or excessive moisture,
dirt, dust and corrosive or explosive atmospheres.
SPECIFICATIONS – ENCLOSURE
EmersonClimate.com/FlowControls

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson FD113 and is the answer not in the manual?

Emerson FD113 Specifications

General IconGeneral
BrandEmerson
ModelFD113
CategoryController
LanguageEnglish

Related product manuals