EasyManuals Logo
Home>Emerson>Measuring Instruments>FloBoss 104

Emerson FloBoss 104 Safe Use Instructions

Emerson FloBoss 104
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
Safe Use Instructions Emerson FloBoss 104 Flow Manager
Part D301733X012
February 2018
2 www.Emerson.com/RemoteAutomation
Specifications
POWER
External Power Charging Input: 8-28 V dc, reverse
polarity protection.
Input Current: 10-15 mA nominal. 20 mA at 100% duty
cycle (battery charging not included).
ENCLOSURE
Housing and Cap: Die-cast aluminum alloy with iridite
plating and paint. Stainless steel (CF8M) version
available.
ENVIRONMENTAL
Operating Ambient Temperature: -40 to +75C.
LCD Display: -20 to +75C.
Storage Temperature: -50 to +85C.
Operating Humidity: 5 to 95%, non-condensing.
WEIGHT
4.30 kg (9.5 lbs) (aluminum)
APPROVALS:
ATEX Version (Flameproof & Type n)
Evaluated per Approval standards:
(Flameproof) (Type n)
EN 60079-0 (2012) EN 60079-0 (2012)
EN 60079-1 (2007) EN 60079-15 (2010)
IEC 60529 IEC 60529
Certified by LCIE as Model W40116.
ATEX Cert LCIE 03ATEX6221 X/06
ATEX Cert LCIE 13ATEX1033 X/01
Product Markings for Hazardous Locations:
Ex d IIB T5 Gb (-40°C ≤ T
amb
+75°C), IP66
Ex nA IIB T3 Gc (-40°C T
amb
+75°C), IP66
II 2/3 G. 0081
Specifications
IECEx Version (Flameproof and Type n)
Evaluated per Approval standards:
IEC 60079-0 (2011)
IEC 60079-1 (2007)
IEC 60079-15 (2010)
IEC 60529
Certified by CSA as Model W40149.
IEC Cert IECEx LCI 08.0039 (Flameproof)
IEC Cert IECEx LCI 08.0015 (Type n)
Product Markings for Hazardous Locations:
Ex d IIB T5 Gb (-40°C T
amb
+75°C), IP66
Ex nA IIC T3 Gc (-40°C T
amb
+75°C), IP66.
IECEx Version (Type n Only)
Evaluated per Approval standards:
IEC 60079-0 (2011)
IEC 60079-15 (2010)
IEC 60529
Certified by CSA as Model W40150.
IEC Cert IECEx LCI 08.0015 (Type n)
Product Markings for Hazardous Locations:
Ex nA IIC T3 Gc ((-40°C T
amb
+75°C ), IP66.
The following tools are required for installation,
maintenance, and troubleshooting:
Personal computer running Microsoft
®
Windows
®
7,
Windows 8.1, or Windows 10 and Emerson Field Tools
configuration software (providing ROCLINK 800
configuration software).
Phillips (cross-head) screwdriver.
Flat-head screwdriver.
Hex socket wrench (M4).
1. You receive the FloBoss 104 in a box. Remove it from
the box.
2. Find a suitable location for the FloBoss 104. When
choosing an installation site, be sure to check all
clearances. Provide adequate clearance for wiring and
service. The optional LCD should be visible and accessible
for the on-site operator. See Figure 8.
3. Mounting of the FloBoss 104 can be accomplished
using one of the following methods:
Pipestand mounted to a 2-inch pipestand. Use the
standard Rosemount 2" (50mm) pipe mounting kit (with
impulse tubing connecting the FloBoss 104 to the meter
run). Ensure that the pipestand meets all weight
requirements and installation conforms to local building
codes. See Figure 9.

Other manuals for Emerson FloBoss 104

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson FloBoss 104 and is the answer not in the manual?

Emerson FloBoss 104 Specifications

General IconGeneral
BrandEmerson
ModelFloBoss 104
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals