EasyManuals Logo
Home>Emerson>Control Unit>OMB

Emerson OMB User Manual

Emerson OMB
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
FEATURES
Self contained unit with oil level sensor and integral solenoid to
manage oil level supply
Hall-effect sensor for precise measurement of oil level
Alarm and status indication by LEDs
SPDT output contact for compressor shutdown or alarming
Easy installation by sightglass replacement
Adapters suitable for various types of compressors including
conventional and scroll compressors
• Signalgeneratedbygravitybasedoat–notpronetoerrorsfrom
foaming like optical sensors
• Sacricialmagnetforreliableoperation
SAFETY INSTRUCTIONS
WARNING: Before opening any system, make sure the pressure in the
system is brought to and remains at atmospheric pressure. Failure to
comply can result in personal injury and/or system damage.
WARNING: The OMB/C operates by using a strong magnetic sensor. It
is important to keep the control free of any steel or iron particles which
could accumulate on it during installation. These may hamper or prevent
the control from operating.
1. Read installation instructions thoroughly. Failure to follow instructions
may result in product failure, system damage, or personal injury.
2. Do not open system under pressure.
3. EnsuresupplyvoltageiswithinspeciedOMB/Climits.
4. Disconnect supply voltage from system/OMB/C before installation/
service. Comply with local electrical regulations when wiring OMB/C.
5. Do not exceed maximum working pressure.
6. Keep temperature within nominal limits.
7. Workshouldbeperformedbyqualiedservicepersonneloralicensed
contractor.
INSTALLATION INSTRUCTIONS
1. Read installation instructions thoroughly.
2. Assure that you have the appropriate mounting adapter kit for the
compressor. See adapter kit instruction sheet (PA-00316) for choosing
proper adapter and installation instructions.
3. O-ring replacement kit (KS30368) can be used on the OMB, OMC and
W-OLC controls.
4. If replacement of OMB or OMC is required, replace like for like
OMB/C Oil Management Control
Instruction Sheet
PA-00388
INSTRUCTIONS FOR FIELD CHANGEOUT OF
OMB OR OMC OIL CONTROL
This instruction has been developed to minimize down time based
uponactualeldexperience.Readthroughtheentireinstructionbefore
proceeding with the change-out.
Tools Recommended: 7/16" nut driver; 7/16" open-end wrench;
adjustable wrench; slotted screwdriver; wire stripper; manifold
gauge set; refrigeration valve wrench (Additional items which may be
required depending on application: 1' of ¼" refrigerant grade copper
tubing.2-¼"brassarenuts;aringtool;3/8"maleareby¼"female
areadapter;3-electricalwirenuts).
1. Disconnect all electrical power to the compressor.
2. Safely connect gauge bar hoses in the following sequence: discharge
line to backseat port of an adjacent compressor service valve;
common line to oil pressure port on crankcase of compressor on
which control is to be changed; suction line to suction manifold on
compressor rack. (Manifold valves should be closed.)
3. Close discharge, suction, and oil feed service valves on compressor.
4. Open the gauge manifold discharge hand wheel to pressurize the
crankcase to discharge pressure. (Important: Do not exceed
allowable pressure limits set by the compressor manufacturer
for the crankcase.)
5. After pressurizing the crankcase to a safe pressure, close manifold
gage discharge wheel.
6. Open the gage manifold suction wheel to allow the high pressure in
the crankcase to meter the oil into the suction manifold.
7. After the oil is below the sight glass on the compressor crankcase,
close the suction hand wheel and safely reclaim the remaining
refrigerant pressure in the crankcase.
8. After all the pressure is depleted in the crankcase, remove the existing
oil control as follows:
A. Disconnect the electrical leads at the control and label each if wire
color codes change.
B. Removeexibleconduit(ifused)atthejunctionbox.
C. Disconnect the oil supply line. Note: A new one may need to be
fabricated, or an adapter required, if replacing an OMB with an OMC.
D.Removetheangemountingboltswhichholdthecontroltothe
adapter and remove existing control.
OMC
SPECIFICATIONS OMB OMC OMC NH
3
OMC CO
2
Maximum Working Pressure (MWP) 870 psig 1885 psig
Solenoid min/max OPD 0/350 psig 0/1450 psig
Supply Voltage 24V, 50/60 Hz
120V, 220-240V,
50/60 Hz
24V, 120V, 220-240V
50/60Hz
Solenoid Coil EMF
Current Consumption 0.6 Amp (24V)
0.15 Amp (120V),
0.07 Amp (220-240V)
0.6 Amp (24V), 0.15 Amp
(120V), 0.07 Amp (220-240V)
Time Delay for Low Level Signal 10 seconds
Time Delay After Setpoint Recovery 5 seconds
Alarm Delay Time (Including Alarm Contact) 120 seconds
Alarm Switch SPDT
Alarm Contact Rating 10A @ 120VAC 50/60 Hz, 5A @ 250VAC 50/60 Hz, 3A @ 30VDC
Refrigerant Compatibility Class A1 (incl. subcritical CO
2)
Ammonia
Transcritical
CO
2
Refrigerant Temperature -40° to 180°F Maximum
Ambient Temperature - Storage -40° to 120°F Maximum
Ambient Temperature - Intermittent Duty -40° to 120°F Maximum
Oil Supply Fitting
1/4" Male SAE
(Brass)
(Stainless
Steel)
(Brass)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson OMB and is the answer not in the manual?

Emerson OMB Specifications

General IconGeneral
BrandEmerson
ModelOMB
CategoryControl Unit
LanguageEnglish

Related product manuals