¢ Models: AOYG30KBTB, AOYG36KBTB, and AOYG45KBTB
Check point 1. Check connections
Check connection of connector. (Loose connector or open cable)
NOTE: For details of wiring diagram, refer to "Wiring diagrams" in Chapter 2. TECHNICAL DATA
AND PARTS LIST on page 02-33.
Check point 2. Check coil of EEV
Remove connector, check each winding resistance of coil.
Read wire Resistance value
White - Red
46 Ω ± 3.0 Ω
at 20°C
Yellow - Red
Orange - Red
Blue - Red
→ If Resistance value is abnormal, replace EEV.
Check point 3. Check voltage from main PCB
Remove connector and check voltage (DC 12 V)
→ If it does not appear, replace main PCB.
Check point 4. Check noise at start up
Turn on the power and check the operation noise.
→ If an abnormal noise does not show, replace main PCB.
Check point 5. Check opening and closing operation of valve
When valve is closed, it has a temp. difference
between inlet and outlet
Pipe (In)
Pipe (Out)
Hi TEMP.
Normal TEMP.
CLOSE
Example : Hot Gas
If it is open, it has no temp. difference between
inlet and outlet
Pipe (In)
Hi TEMP.
OPEN
Example : Hot Gas
Pipe (Out)
Hi TEMP.
4-3. Outdoor unit Electronic Expansion Valve (EEV) - (03-53) - 4. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ARXG22KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG22KMLA and is the answer not in the manual?

Fujitsu ARXG22KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG22KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals