2) Ceiling height
Select the appropriate ceiling height according to the place of installation.
Function number Setting value Setting description Factory setting
20
00 Standard ♦
01 High ceiling
For the specific height for each setting value, refer to “Installation space” in Chapter "Dimensions" on
page 1.
3) Horizontal louver direction switching for dew condensation prevention
Automatically switches the position of the horizontal louver if the airflow direction is set at lower than
the dew condensation limit position in cooling or drying operation.
Select suitable adjustment position according to the customer’s preference.
Function number Setting value Setting description Factory setting
28
00 Adjust to dew condensation limit position ♦
01 Adjust to cooling standard position
4) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 26°C and the setting value is “03”
(-1.0°C), corrected temp. will be 27°C (26°C - [-1.0°C]).
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting ♦
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C