¢ DIP switch setting
SW100: Remote controller address setting
When operating a number of indoor units by using a wired remote controller, DIP switch set-
ting for assigning unit number to each indoor unit is required.
The slide switches are normally set to make the unit number 00.
Remote
controller
address
Switch number
Factory setting
1 2 3 4
00 OFF OFF OFF OFF
01 ON OFF OFF OFF
02 OFF ON OFF OFF
03 ON ON OFF OFF
04 OFF OFF ON OFF
05 ON OFF ON OFF
06 OFF ON ON OFF
07 ON ON ON OFF
08 OFF OFF OFF ON
09 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON
00 01 02
Remote controller address
Indoor unit
Remote controller
SW101-Switch 1: Setting change prohibited
SW101-Switch 2: Setting change prohibited
SW101-Switch 3: Fan delay setting
When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor
unit fan operation will continue for 1 minute.
Switch 3 Fan delay Factory setting
ON Enabled
OFF Disabled
- 57 -
9-1. Function settings on indoor unit
9. Function settings
DUCT TYPE
ARXG24-45KMLA
DUCT TYPE
ARXG24-45KMLA

Table of Contents

Other manuals for Fujitsu ARXG45KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG45KMLA and is the answer not in the manual?

Fujitsu ARXG45KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG45KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals