1–74 345 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
USB INTERFACE CHAPTER 1: COMMUNICATIONS GUIDE
9. i+1 —> i
10. is i = N? No: go to 3. Yes: go to 11.
11. A —> CRC
Timing Data packet synchronization is maintained by timing constraints. The receiving device
must measure the time between the reception of characters. If 3.5 character times elapse
without a new character or completion of the packet, then the communication link must
be reset (i.e. all slaves start listening for a new transmission from the master). Thus at 9600
baud a delay of greater than 3.5 x 1 / 9600 x 10 x = x 3.65 x ms will cause the
communication link to be reset.
345 supported
functions
The following functions are supported by the 345:
FUNCTION CODE 03 - Read Setpoints
FUNCTION CODE 04 - Read Actual Values
FUNCTION CODE 05 - Execute Operation
FUNCTION CODE 06 - Store Single Setpoint
FUNCTION CODE 07 - Read Device Status
FUNCTION CODE 08 - Loopback Test
FUNCTION CODE 10 - Store Multiple Setpoints
Refer to section 5 of this guide for more details on MODBUS function codes.