EasyManuals Logo

GE af-600 fp User Manual

GE af-600 fp
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #113 background imageLoading...
Page #113 background image
F-12 Motor Thermistor Input
Option: Function:
Select the input to which the thermistor (PTC sensor) should be connected. An analog input option [1] or
[2] cannot be selected if the analog input is already in use as a reference source (selected in par.
F-01 Frequency Setting 1, par. C-30 Frequency Command 2 or par. C-34 Frequency Command 3).
[0] * None
[1] Analog input 53
[2] Analog input 54
[3] Digital input 18
[4] Digital input 19
[5] Digital input 32
[6] Digital input 33
NB!
This parameter cannot be adjusted while the motor is running.
NB!
Digital inputs should be set to “No operation” - see par. E-##.
F-24 Holding Time
Range: Function:
0.0 s* [0.0 - 120.0 s] The function selected in par. H-80 Function at Stop is active in the delay period.
Enter the time delay required before commencing acceleration.
F-26 Motor Noise (Carrier Freq)
Option: Function:
Select the inverter switching frequency. Changing the switching frequency can help to reduce acoustic
noise from the motor.
NB!
Switching frequencies higher than 5.0 kHz lead to automatic derating of the maximum output of the
frequency converter.
[0] 1.0 kHz
[1] 1.5 kHz
[2] 2.0 kHz
[3] 2.5 kHz
[4] 3.0 kHz
[5] 3.5 kHz
[6] 4.0 kHz
[7] * 5.0 kHz
[8] 6.0 kHz
[9] 7.0 kHz
[10] 8.0 kHz
[11] 10.0 kHz
[12] 12.0 kHz
[13] 14.0 kHz
[14] 16.0 kHz
AF-600 FP High Power Operating Instructions
111
7

Table of Contents

Other manuals for GE af-600 fp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE af-600 fp and is the answer not in the manual?

GE af-600 fp Specifications

General IconGeneral
BrandGE
Modelaf-600 fp
CategoryDC Drives
LanguageEnglish