P40 Agile P14D, P14N, P94V Version History
P40Agile-VH-EN-9 3
Major Minor
50 H A
April-13
· Original Issue
TG8612C
·
Agile Relay issue following a failure: Error/Lockout 7104:2000/reboot
· IEC 61850 - Connection / Disconnection issues
· DNP3oE Versions - Courier Tunnelling doesnot work (AGP140-46)
· Company name is still AREVA in DNP3 build.
·
Ethernet application (IEC61850 + DNP3oe) crashes if a Courier tunnel is continuously opened/closed
· Object 0 variations: 219, 222, 245 and 247 are incorrect.
· QNX kernel can delay user threads for up to 10ms.
·
IEC61850 Select Before Operate Incorrect Behaviour
· With e-terra scada system, the P40 Agile data model extraction stops at Measurments/PriFouMMXU1$CF
· Unextracted events are lost on RP1, following relay reboot, using a DNPOE build.
·
Incorrect response to Object 2 Variation 3 request for Binary Input Event with Relative Time
· IEEE Floats are wrong at modbus interface.
·
Downloading a settings file reverts settings temporarly to setting group 1
P14D-B/G/L/Z-TM-EN-1
· The map of IEC61850 data model for P34x has errors in Function.
P14N-B/Z-TM-EN-1
· P94V operation on UF
P94V-B/P-TM-EN-1
· DNP3OE Versions - Command management during IED disconnection / connection
· CB Fail trip may fail to operate under faults with DC transient offsets
· IEC 61850 Client disassociation while reading PloGGIO1$CO block in P14D IEDs
· IEC61850 Measurements negative values rounding error
·
Agile latch reset when setting group is changed
· What to do with Pending Reports when BufTm>0? Ed1
· Undervoltage programmable curve not using standard template used by other Px4x relays
·
The VCO Status, cell [3582], for the Voltage Controlled Overcurrent isn't updated after a change. The change
takes effect after a power cycle or change to V Dep OC V<1 Set.
· ISEF, IEF and anything related are not scaled properly when the CT ratio is 5A.
· EF directional function fail to trip
P14DH 53A IEC61850-8-1 Level B Conformance Failure/Issue
50 K A April-2016
DNP Over Ethernet Application Crash after many days of Polling
DNPOE after operated some DI and AI events at the same time ,the relay Ethernet board seems locked
and after a while the relay reboot.
FA Steady Fault - Incorrect Assertion
P14DZ HiZ Function asserting incorrectly (CHA HiF)
Incorrect Burst Count - HiF Detection
High Impedance Fault Maloperation
HIF CHA Hysteresis is not correctly set
HIF Burst Threshold is not reset after the adaptive threshold is disabled
50 June-15AJ
Relay type: Agile P14N, P14D and P94V
Software
Version
Hardware
Suffix
Original Date of
Issue
Description of Changes Technical Documentation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P40 Agile P14D and is the answer not in the manual?

GE MiCOM P40 Agile P14D Specifications

General IconGeneral
BrandGE
ModelMiCOM P40 Agile P14D
CategoryRelays
LanguageEnglish

Related product manuals